Troubleshooting by Error Code
SiME341909EA
226
Part 6 Service Diagnosis
Reference
CHECK 4
Refer to page 264.
YES
Recheck for the compressor and the
refrigerant system.
NO
Replace the inverter PCB.
RXQ6-12AR: A3P
RXQ14/16AR: A3P, A6P
NO
YES
NO
The internal
wiring of the compressor
coil is defective.
Replace the compressor.(
#
1)
YES
Is the
insulation
resistance of the
relevant compressor
100 k
Ω
or
more?
Refrigerant is
stagnated. (The unit is
out of power supply for
more than 6
hours.)
Replace the compressor.(
#
1)
#
1
RXQ6-12AR: M1C
RXQ14/16AR: M1C, M2C
NO
Solve the refrigerant stagnation.
(Power should be supplied for more
than 6 hours.)
YES
CHECK 4
Is the power
transistor normal?
A