Troubleshooting by Error Code
SiME341909EA
232
Part 6 Service Diagnosis
5.47 Inverter Radiation Fin Temperature Abnormality
Applicable
Models
All outdoor unit models
Error Code
P4
Method of Error
Detection
Detect the resistance of the following thermistors during the compressor stops running:
(1) Radiation fin thermistor
(2) Thermistor located in PCB circuit
Error Decision
Conditions
When the resistance of the thermistor comes to a value equivalent to open or short circuit.
Error is not decided while the unit operation is continued.
P4
will be displayed by pressing the inspection button.
Supposed
Causes
Defective radiation fin temperature thermistor
Defective inverter PCB
Defective fan PCB
Defective compressor
Defective fan motor