Troubleshooting by Error Code
SiME341909EA
244
Part 6 Service Diagnosis
5.55 Transmission Error between Outdoor Units
Applicable
Models
All outdoor unit models
Error Code
U7
Method of Error
Detection
Microcomputer checks if transmission between outdoor units is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Connection error of transmission wirings between outdoor unit and external control adaptor
for outdoor unit
Connection error of transmission wirings between outdoor units
Defective outdoor unit main PCB
Defective external control adaptor for outdoor unit