SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
251
5.58 Improper Combination of Indoor Unit and Outdoor Unit,
Indoor Unit and Remote Controller
Applicable
Models
All indoor unit models
All outdoor unit models
Error Code
UA
Method of Error
Detection
A difference occurs in data by the type of refrigerant between indoor and outdoor units.
The number of indoor units connected is out of the allowable range.
Error Decision
Conditions
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Supposed
Causes
Excess of connected indoor units
Defective outdoor unit main PCB
Mismatch of the refrigerant type of indoor and outdoor unit.
Setting of outdoor unit main PCB was not carried out after replacing to spare PCB.
Troubleshooting
Ens
u
re the s
ub
code or
the lamp display of
monitor mode, and then
go to the follo
w
ing:
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Go to Diagnosis Flo
w
chart-1.
(Connection of excess indoor
u
nits)
Go to Diagnosis Flo
w
chart-2.
(Connection of incorrect models
of indoor
u
nits)
Go to Diagnosis Flo
w
chart-3.
(Improper com
b
ination of o
u
tdoor
u
nits)
Go to Diagnosis Flo
w
chart-4.
(
W
rong connection)
Go to Diagnosis Flo
w
chart-5.
(M
u
lti system com
b
ination error)
UA-17
Error code
S
ub
code
Error code
S
ub
code
Error code
S
ub
code
Error code
S
ub
code
Error code
S
ub
code
UA-1
8
UA-20
UA-21
UA-31
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...