SiME341909EA
Troubleshooting by Error Code
Part 6 Service Diagnosis
243
Reference
5.54 Transmission Error between Remote Controller and
Indoor Unit
Applicable
Models
All indoor unit models
Error code
U5
Method of Error
Detection
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time.
Supposed
Causes
Transmission error between indoor unit and remote controller
Connection of 2 main remote controllers (when using 2 remote controllers)
Defective indoor unit PCB
Defective remote controller PCB
Transmission error caused by noise
Troubleshooting
Refer to page 41 for Main/Sub setting.
Control by 2
remote controllers
Main/Sub
setting of both
remote controllers is
set to Main.
All indoor unit
PCB microcomputer
normal monitors
blinking
Resets
normally when
power supply is turned
OFF temporarily.
NO
NO
NO
YES
NO
Replace the indoor unit
PCB.
Set one of the remote
controllers to Sub, turn OFF
the power supply temporarily,
then restart operation.
The error could be produced by
noise. Check the surrounding
area and restart operation.
The error could be produced by
noise. Check the surrounding
area and restart operation. (Ex.:
Heavy-duty wireless equipment,
etc.)
Normal.
Normal.
NO
NO
YES
YES
YES
Replace the remote controller
and restart operation.
YES
Replace the indoor unit PCB
and restart operation.
Is operation normal?
Is operation normal?
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV X RXQ10ARYFK
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...