• Installation
•
Systems • Installation
8
Introduction
Installation of outdoor units
Caution when installing
1.
Remove the crate from the unit.
2.
Remove the four screws fixing the unit to the pallet.
3.
Lift the unit from the pallet and place it on its installation position.
4.
Fasten the unit in place using four anchor bolts M12.
5.
Remove the upper and lower service plate.
6.
When closing the service panels take care that the tightening
torque does not exceed 4.1 Nm.
7.
Remove the yellow shipping stays from the compressor support
as shown in the figure (2 stays per single compressor). Tighten the
installation bolts firmly again afterwards
.
CAUTION
1
Prepare a water drainage channel around the foundation to drain waste water from around the unit.
2
If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.
3
If the unit is to be installed on a frame, install the waterproofing board within a distance of 150mm under the unit in order to prevent infiltration
of water coming from under the unit.
Do not use
stands to
support the
corners.
(V2887)
NOTE
1
Note : Maximum height of the foundation is 150mm.
(V2357)