Connection Ratio Limits
SYSTEM
TYPE
AIR COOLED
WATER COOLED
ALL VRV-IV (3-PHASE)
VRV-S
PC
Series
T-Series
Indoor
Unit
Type
All FXDQ
All FXMQ(P)
All FXAQ
FXSQ07T-54T
FXSQ-05T
FXZQ-05T
FXFQ-07
FXFQ-09
All
Other
Units
All
Units
All
Units
FXDQ
FXMQ(P)
FXSQ07-54T
FXAQ
FXZQ-05
FXFQ07/09
FXSQ-05T
and All
Other Units
Single
Module
200%
180% 200% 130%
130%
150%
150%
Dual
Module
160% 160%
N/A
130%
Triple
Module*
130% 130%
130%
120%
@36 Ton
Notes:
1.
Minimum Connection Ratio for the RXYQ72TAYCU / REYQ72TAYCU: 70%
2. Minimum Connection Ratio for all other standard Air Cooled and
Water Cooled models: 50%.
3. When systems are designed to >130% connection ratio, indoor units in thermo ON
are set to low fan speed by default. This function can be overridden at commissioning
stage, if desired.
Capacity Index Table
Indoor Unit Size
5
7
9
12
15
18
24
30
36
42
48
54
60
72
96
Indoor Unit Capacity Index
5.8
7.5
9.5
12
15
18
24
30
36
42
48
54
60
72
96
SYSTEM TYPE
AIR COOLED
ALL AURORA (3-PHASE)
Indoor Unit
Type
All FXDQ, All FXMQ(P), All FXAQ
FXSQ07T-54T
FXSQ-05T
FXZQ-05T
FXFQ-07
FXFQ-09
All Other
Units
Single Module
200%
180%
200%
Dual Module
160%
160%
Note:
Minimum Connection Ratio for all AURORA models is 70%
Summary of Contents for VRV
Page 1: ...VRV Reference Guide ...
Page 4: ......
Page 5: ...System Overview ...
Page 18: ...Piping and Electrical Wiring Guide Condensing Unit Pipe Connections 18 ...
Page 22: ......
Page 23: ...System Selection ...
Page 41: ...Design Optimization ...
Page 53: ...Controls Standards ...
Page 65: ...65 Notes ...
Page 66: ...66 Notes ...
Page 67: ......