Design Criteria:
Water loop design is the responsibility of the engineer. However, two
facts are needed from Daikin:
The minimum & maximum entering water temperatures:
»
50 °F-113 °F for Cooling
»
23 °F-113 °F for Cooling on a Geothermal System
»
50 °F-113 °F for Heating
»
14 °F-95 °F for Heating on a Geothermal System
A suitable water flow rate:
»
13.2 gpm to 39 gpm per module Boiler & Tower System
»
21 gpm to 39 gpm per module with glycol use
* (Be aware that conditions need to be met when EWT for heating is
required below 50°F – seek assistance for these applications)
Other consideration:
»
When VRV is to be applied with an open loop system, a 3rd party
heat exchanger is required to ensure the plate heat exchanger of
the VRV condensing unit operates in a closed loop system.
»
The VRV condensing units have a heat output into the adjacent
mechanical room (see table). Where multiple units are placed in
an enclosed area, any potential heat buildup must be addressed
(either with adequate ventilation or even a fan coil unit). RWEQ_TA
series units have the ability to configure the unit to reject this heat
to the refrigerant circuit. See Installation manual for further details.
»
From the CU pipe connection to the fan coils, the equipment,
controls & selection process is identical to air cooled VRV.
Module Model
Ventilation Load (BTU/hr)
RWEYQ72PC
2,200
RWEYQ84PC
2,450
RWEQ96TA
2,730
RWEQ120TA
3,412
RWEQ144TA
4,436
Summary of Contents for VRV
Page 1: ...VRV Reference Guide ...
Page 4: ......
Page 5: ...System Overview ...
Page 18: ...Piping and Electrical Wiring Guide Condensing Unit Pipe Connections 18 ...
Page 22: ......
Page 23: ...System Selection ...
Page 41: ...Design Optimization ...
Page 53: ...Controls Standards ...
Page 65: ...65 Notes ...
Page 66: ...66 Notes ...
Page 67: ......