TOTAL PIPING
REQUIRED
REFNET JOINT
SETS
BRAZED
CONNECTIONS
BSQ BOX
HANGING RODS
................................
................................
................................
................................
696 ft
11
186
48
Using single port boxes provides the ultimate in flexibility for branch box location. This method
ensures a much reduced total piping. It also significantly reduces the amount of refrigerant
required in the system – critical if the allowable level of refrigerant is a major factor
16'
16'
16'
16'
48'
16'
10'
10'
10'
10'
10'
10'
4'
TOTAL PIPING
REQUIRED
REFNET JOINT
SETS
BRAZED
CONNECTIONS
BSQ BOX
HANGING RODS
1392 ft
0
54
4
...however, if it is possible to incorporate multiport boxes, a reduction in installation costs
can be realized. This example, using a single 12 port multi-box, requires no refnet joints and
demonstrates a marked reduction in brazed connections and hanging rods
12'
28'
44'
60'
76'
92'
12'
28'
44'
60'
76'
92'
12 port
................................
................................
................................
................................
48'
45
Single or Multi BSQ Boxes?
Optimized Selection of BSQ Boxes
When selecting HEAT RECOVERY BRANCH SELECTOR BOXES there
is a limitless number of ways to group indoor units
= BSQ Box
= Indoor Unit