Troubleshooting by Indication on the Remote Controller
123
CHECK 16
Check fan motor
connector (power supply
wire)
A
YES
NO
The
resistance
value between
UVW phases of fan
motor is out of balance,
or short circuit
between UVW
phases.
Replace the
corresponding
fan motor.
YES
NO
No
continuity of fuse on
main PCB.
Replace the PCB.
YES
YES
NO
Unable to
rotate the fan
manually with ease
when removing the
connector of the
fan motor.
Replace the
corresponding
fan motor.
NO
Resistance
value between
the power supply wire
terminal of fan motor and
the motor frame
(metal) is 1M
Ω
and below.
Replace the
corresponding
fan motor.
B