Troubleshooting by Indication on the Remote Controller
174
3.41
J6
Outdoor Unit Heat
Exchanger Thermistor
Abnormality
Remote Controller Display
J6
Applicable Models
VRVII, II-S, III, III-S and III-Q Series
Method of Error Detection
Error is detected from the temperature detected by the
outdoor unit heat exchanger thermistor.
Error Decision Conditions
When a short circuit or an open circuit in the heat
exchanger thermistor is detected.
Supposed Causes
Defective thermistor for outdoor unit coil
Defective outdoor unit PCB
Defective thermistor connection