Troubleshooting by Indication on the Remote Controller
246
Troubleshooting
NO
Is the
type of the
compressor inverter
PCB correct?
Replace it with
the correct
compressor
inverter PCB.
YES
YES
NO
NO
Is the
type of the fan
inverter PCB
correct?
Replace it with
the correct fan
inverter PCB.
YES
Is the
setting of dip
switches when replace
the main PCB
correct?
Set the DIP
switches
correctly.
(After setting:
Reset the power
supply)
YES
NO
Does the
preparation
indication lamp (H2P)
on the main PCB
turn OFF?
Rectify the
connection
wiring.
Replace the
outdoor unit main
PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.