Troubleshooting by Indication on the Remote Controller
357
Check for causes of wet operation.
Referring to the Fault Tree Analysis (FTA) shown below,
probe the defective points.
CHECK 5
[In cooling]
Indoor unit
electronic
expansion
valve opens
too much. (
∗
1)
[In heating]
Outdoor unit
electronic
expansion
valve opens
too much. (
∗
2)
←
Are the coil resistance and
insulation normal?
←
Is the connector properly
connected?
Are the thermistor
resistance characteristics
normal?
←
Is the connector properly
connected?
Are the thermistor
resistance characteristics
normal?
Defective
valve coil
Defective
valve body
Defective gas
pipe
thermistor of
indoor unit
Defective
liquid pipe
thermistor of
indoor unit
Defective
service
monitor PCB
Defective
indoor unit
electronic
expansion
valve
Defective
control
←
Are the coil resistance and
insulation normal?
←
Are the electric
characteristics normal?
←
Is the connector properly
connected?
Are the thermistor
resistance characteristics
normal?
←
Is the pressure value
checked with the Service
Checker corresponding to
the measurement value of
the pressure sensor?
Defective
valve coil
Defective
valve body
Defective low
pressure
sensor
Defective
suction pipe
thermistor
Defective
service
monitor PCB
Defective
outdoor unit
electronic
expansion
valve
Defective
control
Defective
control of
superheated
degree
Wet
operation
Defective crankcase
heater
Frequent ON/OFF of
compressor
Refrigerant
accumulation
Overcharge of
refrigerant
←
Refer to [CHECK 11]
A