Troubleshooting by Indication on the Remote Controller
311
Remote Controller Display
U7
Applicable Models
VRVII, -WII and -WIII Series
Method of Error Detection
Micro-computer checks if transmission between indoor
unit and remote controller is normal.
Error Decision Conditions
When transmission is not carried out normally for a
certain amount of time
Supposed Causes
Improper connection of transmission wiring between
outdoor (outside) unit and external control adaptor for
outdoor (outside) unit.
Improper cool/heat selection
Improper cool/heat unified address (outdoor (outside)
unit, external control adaptor for outdoor (outside) unit)
Defective outdoor (outside) unit PCB
Defective external control adaptor for outdoor
(outside) unit
Improper connection of transmission wiring between
outdoor (outside) units of multi outdoor (outside) unit
connection.