Surge Capacitors
All low voltage units (except those with solid state starters or VFDs) are supplied with standard surge
capacitors to protect compressor motors from electrical damage resulting from high voltage spikes.
For free-standing starters, factory or customer supplied, the capacitors are mounted in the motor terminal
box and must be connected to the motor terminals with leads less than 18 inches (460 mm) long when the
motor is being wired.
Field Wiring Diagram
Figure 8