IOM 1281-2 • CENTRIFUGAL WATER CHILLERS 60 www.DaikinApplied.com
Operation
Condenser Pump #1
Fault
No flow indicated for (5 sec) with Condenser Pump
#1 ON AND [the other pump is available (per the
evaporator Pump SP) AND has not faulted]
Rapid Stop/No Start
Condenser flow not detected. Causes: improper
pump wiring
Manual
Condenser Pump #2
Fault
No flow indicated for (5 sec) with Condenser Pump
#2 ON AND [the other pump is available (per the
evaporator Pump SP) AND has not faulted]
Rapid Stop/No Start
Condenser flow not detected. Causes: improper
pump wiring
Manual
Table 20: Warning Alarms
Screen Text
Occurs When
Action Taken
Troubleshooting
Clear
Low Evaporator Pressure –
Inhibit Loading
Pressure < Low Evap Pressure–Inhibit setpoint
Inhibit loading
Auto
Low Evaporator Pressure –
Unload
Pressure < Low Evap Pressure–Unload setpoint
Unload
Auto
Evaporator Freeze Protect
Evap Sat Refr Temp < Evaporator Freeze SP
Start evaporator pump
and oil pump
While unit is not running
Auto
Condenser Freeze Protect
Cond Sat Refr Temp < Condenser Freeze SP
Start condenser pump
and oil pump
While unit is not running
Auto
Liquid Line Refrigerant
Temperature Sensor Fall
Warning
Sensor is shorted or open
Unit continues to run,
performance may be
affected
Check for loose wires or failed sensor
Auto
Entering Evaporator Water
Temperature Sensor Fall
Warning
Sensor is shorted or open
Unit continues to run,
performance may be
affected
Check for loose wires or failed sensor
Auto
Leaving Condenser Water
Temperature Sensor Fail
Warning
Sensor is shorted or open
Unit continues to run,
performance may be
affected
Check for loose wires or failed sensor
Auto
Entering Condenser Water
Temperature Sensor Fail
Warning
Sensor is shorted or open
Unit continues to run,
performance may be
affected
Check for loose wires or failed sensor
Auto