IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR 44 www.DaikinApplied.com
Unit Controller
The ECWT is < Stage #X ON (Temp) set point – Stage
Differential (Temp) set point
Bypass valve position is < the Stage Down @ set point (only if
Valve/VFD Control set point = Valve Stage)
VFD Speed is < the Stage Down @ set point (only if Valve/VFD
Control set point = VFD Stage OR
Valve SP/VFD Stage)
Each stage up or stage down event will restart both the
stage up and stage down timers. Only one fan output will be
switched at a time (except that all outputs switch OFF when the
condenser pump state equals OFF).
Cooling Tower Bypass Valve
When the Valve/VFD Control set point is set to None OR
VFD Stage, this output will be set to 0. Otherwise, it shall be
controlled as described below.
Initial Valve Position
When the condenser pump is not in the RUN state, the valve
output will be set as a function of entering condenser water
temperature (ECWT)) per the following graph.
Operation After Start
When the condenser pump is in the RUN state, the valve
output will be controlled in one of two modes as specified by
the Valve/VFD Control set point. The controlled parameter
will be the condenser entering water temperature. When the
desired output signal varies from 0 to 100%, the output voltage
will vary as shown below.
0 to 10 VDC (Valve Type = NC to tower)
10 to 0 VDC (Valve Type = NO to tower)
Valve Set Point Mode
This mode is operational when the Valve/VFD Control set point
is set to Valve Set Point OR Valve SP/VFD Stage. In this mode
the valve output is varied with a proportional-derivative (PD)
algorithm (with dead band) in order to maintain the controlled
parameter (CP) at the desired value. The output is always
limited between the Valve Control Range (Min) set point and
the Valve Control Range (Max) set point. A valve increment
shall be computed once every 5 seconds according to the
following equation.
Increment = [(Error) * (Error Gain set point)] + [(Slope) * (Slope
Gain set point)]
Where: Error = ECWT – Valve Set Point Slope = (Present
CP) – (Previous CP)
When the Error is > the Valve Deadband set point, the valve
position analog output (% of full scale) is updated according to
the following equation.
New %Position = Old %Po Increment/10.
Valve Stage Mode
This mode is only operational when the Valve/VFD Control
set point is set to Valve Stage. In this mode the valve output
is controlled as for Valve Set Point mode (above) except that
the active set point for the controlled parameter is selected
according to the following table.
Number Of Fans ON
Active Set Point
0
Valve Set Point
1
Stage #1 ON
2
Stage #2 ON
Cooling Tower Fan VFD
When the Valve/VFD Control set point is set to None, Valve Set
point, OR Valve Stage, this output will be set to 0. Otherwise,
it will be controlled in a manner identical to Valve Stage Mode
(above) except that (1) it will be kept at zero until the first fan
stage is ON and (2) the following set points do not apply.
Valve Control Range (Min)
Valve Control Range (Max)
Valve Type
Compressor Start/Stop Timing
This section determines when to start or stop a compressor.
There are two separate functions used, one for staging up and
one for staging down.
Stage Up Now
The
Stage Up Now
flag is set based on the following tests:
If Unit mode = Cool AND
no compressors are running AND
LWT error > Start delta + 0.5 * Control Band AND
Motor Protect Timer expired AND
Stage up timer expired THEN
Stage Up Now
= True
If Unit Mode = Cool AND
At least one compressor is running AND
LWT error > 0.5 * Control band AND
Pulldown rate <= Max pulldown rate AND
Compressors running < unit capacity limit AND
Stage up timer expired THEN
Stage Up Now
= True
Summary of Contents for WGZ030DW
Page 4: ......
Page 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Page 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Page 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...