SINGLE SCREW CHILLERS IMM
20
Engineered for Flexibility and Performance
Fig.6-1
If chiller is installed in the building of the middle layer where excessive vibration may occur, please
use the spring anti-vibration device. Daikin offers spring isolators according to the user's
requirements.
A
L
Adjusting bolt
Foundation
Chiller Foot
B
Fig.6-2
In Fig.6-2, it is used for the spring isolator mounting, in which AB is the edge length of the spring
isolator and L is the distance between the two bolt holes on the bottom. Anchor the spring isolator
with bolts at two holes on the bottom plate, and then tighten the lock nuts.
Spring isolator can be placed directly on the concrete ground as the rubber can prevent vibration
and slipping. If there are spring isolators, anchor bolts will not be required.
The location of the four spring isolators is the same to anti-vibration pads shown in Fig.6-1, the two
holes in each corner match the two bolts on spring isolators.