Installation Guide

Daintree

®

 Networked Wireless Adapter (WA100-PM)

11

Figure 17: 

Emergency and Regular Light Fixtures: Wiring 

to Dim while Regular Power is Available

In this application, the WA100-PM is powered by the Regular 

power circuit and is installed inside the Regular Light Fixture. 

While Regular power is supplied to the RRU-2 the WA100-PM 

provides switched On/Off power to the Regular Light Fixture.
The WA100-PM also controls dimming to the Regular and  

Emergency Light Fixture. The 0-10V dimming circuit from the 

WA100-PM is brought into the Emergency Light Fixture. The 

Emergency Light Fixture is powered by the Emergency  

power circuit.
When the RRU-2 senses loss of Regular power, the RRU-2 

disconnects the 0-10V output from the WA100-PM and the

Emergency Light Fixture operates at maximum output from the 

Emergency power circuit . (Note: If the RRU-2 is not installed, the 

Emergency Fixture will dim to minimum because the WA100-PM 

0-10V output shorts when the adapter loses power.)

7

Wiring Continued

Set DIP switches and perform Installation Test appropriate 

to 0-10v dimming and connected sensors.

In the wiring diagram here, while Regular power is supplied to the 

LVS model RRU-X-UM the WA100-PM provides switched On/Off 

power and 0-10V dimming control to the fixture driver or ballast.
When the RRU-X-UM senses loss of Regular power it passes 

Emergency power directly to the fixture. It disconnects the 

WA100-PM switched output and disconnects the WA100-PM 

dimming control so that the fixture will operate at maximum 

output during the power failure.

Figure 16: 

Bypass WA100 switched power and 0-10V 

dimming control during power failure

Summary of Contents for GE Current WA100-PM

Page 1: ...network and controls lights The WA100 PM is an AC powered device that provides On Off switching as well as 0 10V analog dimming control for LED drivers and ballasts It also provides power for low volt...

Page 2: ...n Off no dimming provides On Off control using its line voltage Switched Load connection and its low voltage digital output to an external relay Note both outputs are switched at the same time in this...

Page 3: ...he Black Hot flying lead and the Red Switched Load flying lead are 14AWG The White Neutral flying lead is 18AWG Low voltage 22AWG flying leads provide for connections to supply low voltage power and c...

Page 4: ...Wireless Adapter WA100 PM 4 Figure 3 Wiring Identification Figure 4 Dimming Light Fixtures 7 Wiring Continued Perform Installation Test Suite 1 DIP Switches Driver Type On Off 0 10V dimming Wired Sens...

Page 5: ...s Occupancy Sensor configuration This configuration allows the WA100 PM to provide automatic On Off switching based on occupancy Set occupancy sensor for minimum time delay 7 Wiring Continued Perform...

Page 6: ...or for minimum time delay Figure 8 Dimming Light Fixture s Photosensor configuration This configuration allows the WA100 PM to provide automatic 0 10V dimming control and to switch light fixtures On O...

Page 7: ...ght Fixture s and Switch configuration This configuration allows the WA100 PM to provide 0 10V dimming control and to switch light fixtures On Off It also provides manual On Off control through a low...

Page 8: ...ching This configuration allows the WA100 PM to alternate in switching separate drivers providing no load 0 partial load according to the driver loading or full load 100 Always connect the smaller pro...

Page 9: ...gure 14 208V 2 Pole Phase to Phase wiring This configuration allows the WA100 PM to provide On Off switching of a branch circuit 7 Wiring Continued OFF ON OFF ON Perform Installation Test Suite 1 DIP...

Page 10: ...gure 15 Switching Contactors This configuration allows the WA100 PM to provide On Off switching control to an external contactor 7 Wiring Continued OFF ON Perform Installation Test Suite 1 DIP Switche...

Page 11: ...V output from the WA100 PM and the Emergency Light Fixture operates at maximum output from the Emergency power circuit Note If the RRU 2 is not installed the Emergency Fixture will dim to minimum beca...

Page 12: ...is included with the WA100 PM Affix this label to the outside of the fixture Choose a standard location so that when someone looks for fixtures containing a WA100 PM they will easily find it Using the...

Page 13: ...e 2 Any Driver Occupancy Sensor 1 Press and immediately release the blue Reset button The red Error LED flashes once then pauses and repeats 2 Check that the connected lights cycle On and Off or cycle...

Page 14: ...the green Joined LED and the red Error LEDs begin flashing Test Suite 4 Continued 4 Operate the switch es connected to the WA100 PM and observe that the lights turn On Off and Dim as expected 5 Press...

Page 15: ...own after the sensor s internal time delay expires Therefore set occupancy sensors for the minimum time delay during the WA100 PM installation The red Error LED is flashing once every second DIP switc...

Page 16: ...lug load circuit Wiring for Combination Plug Load Basic Aux Relay and On Off Light In the wiring diagram below the WA100 PM is used to control both an On Off light and a plug load circuit Plug Load Ap...

Page 17: ...plug load circuit Plug Load Applications Continued Perform Installation Test Suite 1 DIP Switches Driver On Off 0 10V dimming Plug Load On Off Wired Sensor None On 1 2 3 4 5 6 2 3 On OFF ON 0 10V Dim...

Page 18: ...t and a plug load circuit Plug Load Applications Continued Perform Installation Test Suite 1 DIP Switches Driver On Off Plug Load On Off Wired Sensor None On 1 2 3 4 5 6 2 4 On OFF ON 0 10V Dimming ou...

Page 19: ...RECT TYPE DISPOSAL OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS WFA100 PM Input Voltage 120 277VAC 50 60Hz Switched Output 15A driver incandescent 120 277VAC Relay 1hp 120 230VAC switched to Hot Ac...

Reviews: