Installation Guide
Daintree
®
Networked Wireless Adapter (WA100-PM)
14
Test Suite 8:
Test Suite 9:
Dimming Photosensor
1.
Press and immediately release the blue Reset button. The
red Error LED flashes once, then pauses and repeats.
2.
Check that the lights connected to the driver cycle from
maximum to minimum brightness then turn Off,
then repeat.
3.
Press and immediately release the blue Reset button again.
The red Error LED flashes three times, then pauses
and repeats.
4.
The light connected to the driver turns On.
5.
Increase the amount of light at the photosensor by shining
a bright light at it. The light’s output is proportional
to the amount of light received by the photosensor.
• For dimming lights, shine a bright light at the
photosensor – the light gets brighter. Cover the
photosensor – the light gets dim.
• For switched lights, cover the photosensor – the light
turns Off. Shine a bright light at the photosensor – the
light turns On.
6.
Press and immediately release the Reset button to exit
testing.
7.
Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button
when the green Joined LED and the red Error LEDs
begin flashing.
Occupancy Photosensor
1.
Press and immediately release the blue Reset button. The
red Error LED flashes twice, then pauses and repeats.
2.
Trigger the occupancy sensor. The green Joined LED turns
On. When the sensor times out the Joined LED
turns Off.
3.
Press and immediately release the blue Reset button again.
The red Error LED flashes three times, then pauses
and repeats.
4.
The green Joined LED begins to flash. Increase the amount
of light at the photosensor by shining a bright light
at it. The green Joined LED flashes at a faster rate.
5.
Press and immediately release the Reset button to exit
testing.
6.
Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button
when the green Joined LED and the red Error LEDs
begin flashing.
Test Suite 4: Continued
4. Operate the switch(es) connected to the WA100-PM and
observe that the lights turn On, Off, and Dim as expected.
5. Press and immediately release the Reset button to exit
testing.
6. Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button
when the green Joined LED and the red Error LEDs
begin flashing.
Test Suite 5:
Test Suite 6:
Test Suite 7:
Occupancy Sensor Only
1.
Press and immediately release the blue Reset button.
The red Error LED flashes twice, then pauses and repeats.
2.
Trigger the occupancy sensor. The green Joined LED turns
On. When the sensor times out the Joined LED turns Off.
3.
Press and immediately release the Reset button to
exit testing.
4.
Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button
when the green Joined LED and the red Error LEDs
begin flashing.
Photosensor Only
1.
Press and immediately release the blue Reset button. The
red Error LED flashes three times, then pauses
and repeats.
2.
The green Joined LED begins to flash. Increase the amount
of light at the photosensor by shining a bright light
at it. The green Joined LED flashes at a faster rate.
3.
Press and immediately release the Reset button to
exit testing.
4.
Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button
when the green Joined LED and the red Error LEDs
begin flashing.
Switch Only (On/Off, Dimming, Alternate Switching or Bi-Level)
1.
Press and immediately release the blue Reset button.
The red Error LED flashes four times, then pauses
and repeats.
2.
Operate the switch connected to the WA100-PM. The
green Joined LED turns On for the duration of the switch
activation (applies to On, Off, and Dim functions).
3.
Press and immediately release the Reset button to exit
testing.
4.
Press and hold the blue RESET button on the WA100-PM
for 3 seconds to reset the unit. Release the button when
the green Joined LED and the red Error LEDs begin
flashing.
10