background image

Installation Guide

Daintree

®

 Networked Wireless Adapter (WA100-PM)

3

5

6

7

Switch Adapter Mode

Occupancy Sensor Time Delays

Wiring

Switch Type

Dimming: 

operating the connected switch generates 

dimming and On/Off signals.

On/Off (no dimming):

 operating the connected switch 

generates On/Off signals.

Alternate: 

operating the connected switch will switch separate 

drivers, providing no load (0%), partial load (one or the other of 

the two loads, according to the driver loading) or full load (100%).

Bi-Level:

 operating the connected switch will switch loads 

independently in a bi-level driver (or 2 drivers), providing no 

load (0%), partial load (according to the driver capability or 

driver loading) or full load (100%).

Light output ID

Light + Switch (driver and switch are the same type): 

the 

connected driver matches the operational capability of the 

switch. For example:

  •  If the Switch type is “Dimming,” a dimming switch and 0-10V  

    dimmable driver are both connected to the WA100-PM.  

 

  See Figure 10.

  •  If the Switch type is “On/Off (no dimming)” an On/Off switch  

    is connected to the WA100-PM digital input and On/Off  

 

    driver(s) are connected to the WA100-PM’s line voltage  

 

    Switched Load connection and/or an external relay 

    connected to the WA100-PM’s low voltage digital output.

  •  If the Switch type is “Bi-Level,” a bi-level driver and bi-level    

    switch connect to the WA100-PM.

No Light (switch only): 

provides wireless adaptation for the 

selected switch type only. No light is connected to the WA100-PM.

Occupancy sensor time delays must be set for minimum. 

When the Daintree Networked is commissioned, time delays 

are set in the Daintree Controls Software (DCS) web application. 

These DCS “Off delays” start counting down after the sensor’s 

internal time delay expires. Therefore, set occupancy sensors for 

the minimum time delay during the WA100-PM installation.

Line voltage wiring connects to the electrical supply circuit and 

to the driver(s). The Black (Hot) flying lead and the Red (Switched 

Load) flying lead are 14AWG. The White (Neutral) flying lead is 

18AWG.
Low voltage 22AWG flying leads provide for connections to 

supply low voltage power and carry control signals to and

from low voltage devices such as switches, dimmers, photocells, 

isolated relays and 0-10V analog dimming driver controls. 

Do 

not connect any single low voltage device to more than one 

WA100-PM. 

While the WA100-PM is in Installation Test mode the low voltage 

devices connected to the WA100-PM directly control the lights 

wired to the same WA100-PM. After you exit Installation Test 

mode, the lights turn On and are NOT controlled by the devices 

connected to the WA100-PM.
After joining the wireless network, the control signals from the 

low voltage devices pass through the WA100-PM and are sent 

wirelessly to the Daintree Networked. Depending on the zone 

and device configuration in the DCS, wireless signals from the 

WAC to the WA100-PM determine the operation of the light(s).

Design Caution

Wireless adapters must always be provided with uninterrupted 

power. Do not install a wireless adapter such as the WA100-PM to 

control an electrical circuit that provides power to other wireless 

devices or adapters. If power to wireless adapters or devicesis shut 

off, control and communication with them is disabled.

Risk of electrical shock. Disconnect all power before installation and 

during servicing. Do not open WA100-PM enclosure; no user-serviceable 

parts inside. All installation and maintenance of line voltage equipment 

must be performed by a qualified electrician. The WA100-PM must be 

installed in accordance with all local, state, and national electrical codes 

and requirements. Wiring connectors are not supplied. UL recognized 

wiring connectors must be used in the installation.

CAUTION

Reducing noise on low voltage (0-10V) wiring
•   Keep wiring as short as practical
•   Keep signal lines separate from mains voltage lines.
•   Reduce the area created by the signal lines and    

  the GND return (i.e., keep them close together).
•   If possible twist the signal line with the GND return.

Summary of Contents for GE Current WA100-PM

Page 1: ...network and controls lights The WA100 PM is an AC powered device that provides On Off switching as well as 0 10V analog dimming control for LED drivers and ballasts It also provides power for low volt...

Page 2: ...n Off no dimming provides On Off control using its line voltage Switched Load connection and its low voltage digital output to an external relay Note both outputs are switched at the same time in this...

Page 3: ...he Black Hot flying lead and the Red Switched Load flying lead are 14AWG The White Neutral flying lead is 18AWG Low voltage 22AWG flying leads provide for connections to supply low voltage power and c...

Page 4: ...Wireless Adapter WA100 PM 4 Figure 3 Wiring Identification Figure 4 Dimming Light Fixtures 7 Wiring Continued Perform Installation Test Suite 1 DIP Switches Driver Type On Off 0 10V dimming Wired Sens...

Page 5: ...s Occupancy Sensor configuration This configuration allows the WA100 PM to provide automatic On Off switching based on occupancy Set occupancy sensor for minimum time delay 7 Wiring Continued Perform...

Page 6: ...or for minimum time delay Figure 8 Dimming Light Fixture s Photosensor configuration This configuration allows the WA100 PM to provide automatic 0 10V dimming control and to switch light fixtures On O...

Page 7: ...ght Fixture s and Switch configuration This configuration allows the WA100 PM to provide 0 10V dimming control and to switch light fixtures On Off It also provides manual On Off control through a low...

Page 8: ...ching This configuration allows the WA100 PM to alternate in switching separate drivers providing no load 0 partial load according to the driver loading or full load 100 Always connect the smaller pro...

Page 9: ...gure 14 208V 2 Pole Phase to Phase wiring This configuration allows the WA100 PM to provide On Off switching of a branch circuit 7 Wiring Continued OFF ON OFF ON Perform Installation Test Suite 1 DIP...

Page 10: ...gure 15 Switching Contactors This configuration allows the WA100 PM to provide On Off switching control to an external contactor 7 Wiring Continued OFF ON Perform Installation Test Suite 1 DIP Switche...

Page 11: ...V output from the WA100 PM and the Emergency Light Fixture operates at maximum output from the Emergency power circuit Note If the RRU 2 is not installed the Emergency Fixture will dim to minimum beca...

Page 12: ...is included with the WA100 PM Affix this label to the outside of the fixture Choose a standard location so that when someone looks for fixtures containing a WA100 PM they will easily find it Using the...

Page 13: ...e 2 Any Driver Occupancy Sensor 1 Press and immediately release the blue Reset button The red Error LED flashes once then pauses and repeats 2 Check that the connected lights cycle On and Off or cycle...

Page 14: ...the green Joined LED and the red Error LEDs begin flashing Test Suite 4 Continued 4 Operate the switch es connected to the WA100 PM and observe that the lights turn On Off and Dim as expected 5 Press...

Page 15: ...own after the sensor s internal time delay expires Therefore set occupancy sensors for the minimum time delay during the WA100 PM installation The red Error LED is flashing once every second DIP switc...

Page 16: ...lug load circuit Wiring for Combination Plug Load Basic Aux Relay and On Off Light In the wiring diagram below the WA100 PM is used to control both an On Off light and a plug load circuit Plug Load Ap...

Page 17: ...plug load circuit Plug Load Applications Continued Perform Installation Test Suite 1 DIP Switches Driver On Off 0 10V dimming Plug Load On Off Wired Sensor None On 1 2 3 4 5 6 2 3 On OFF ON 0 10V Dim...

Page 18: ...t and a plug load circuit Plug Load Applications Continued Perform Installation Test Suite 1 DIP Switches Driver On Off Plug Load On Off Wired Sensor None On 1 2 3 4 5 6 2 4 On OFF ON 0 10V Dimming ou...

Page 19: ...RECT TYPE DISPOSAL OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS WFA100 PM Input Voltage 120 277VAC 50 60Hz Switched Output 15A driver incandescent 120 277VAC Relay 1hp 120 230VAC switched to Hot Ac...

Reviews: