BEFORE YOU BEGIN 

Read these instructions completely and carefully.

Save these instructions for future use.

1

Installation Process

Installation Guide 

WFA100-SN  |  DT111

1. Disconnect power before installation.

 Turn off all power 

  to affected light fixtures by turning off circuit breakers.  

 

  Confirm that power is off at all light fixtures before 

  continuing installation.

2.

 

IMPORTANT: 

Use the provided Fixture and Plan labels to  

  identify the wireless-adapted fixture location. Attach the 

Fixture

  

  label to the outside of the fixture. Attach the 

Plan

 label at the    

  fixture location on the facility floor plan.

4.

 Connect low voltage wiring from the WFA100-SN to the ballast,  

  and sensors as appropriate for your application. See 

Wiring

    

  (pages 2-7).

5. 

Connect line voltage wiring from the supply circuit to the 

  WFA100-SN and from the WFA100-SN to the ballast.  

 See 

Wiring

.

Risk of electrical shock. Disconnect power before servicing or  

installing product. 

Install in accordance with National Electric Code and local codes.

WARNING

Risk of injury. Wear safety glasses and gloves during installation and 

servicing.

CAUTION

The 

Daintree Wireless Fixture Adapter (WFA100-SN) 

forms part of Daintree Networked in commercial and industrial 

buildings. It transmits and receives messages over the wireless 

ZigBee

®

 network and controls lights.

Fixture adapters are AC powered devices that provide On/Off 

switching as well as 0-10V analog dimming control for ballasts 

and LED drivers. The WFA100-SN also provides power and signal 

connections for low voltage occupancy sensors and photosensors 

(daylight harvesters). The WFA100-SN automatically configures 

itself for the type of sensor(s) connected to it.
The WFA100-SN provides the wireless adaptation that enables 

connected devices to communicate with the rest of the 

wireless lighting control solution. The adapter also serves as 

a communication router in the ZigBee wireless mesh network. 

Control signals pass between the adapter and the Wireless 

Area Controller in the Daintree Networked platform.

Figure 1: LED Indicators

Power

LED

Joined

LED

Error

LED

Error/Test 

— On when the Wireless Adapter is in an error state. 

Flashes to indicate unit Reset and during Installation Test Mode (red).

Joined 

— On when the Wireless Adapter has joined a ZigBee

®

 network. 

Flashes to indicate Reset and during sensor Installation Test Mode (green).

Power 

— On when power is applied to the Wireless Adapter (green). 

 

LED Indicators

6.

 Check load circuits then turn on the circuit breakers to power

  up the WFA100-SN. The light connected to the WFA100-SN    

  turns On when power is initially applied (and when power is    

  restored after a power failure).

7.

 Ensure the WFA100-SN green Power       LED is On. 

8.

 Press and hold the Reset button on the WFA100-SN for  

  3 seconds to reset it. Release the button when the green 

  Joined       LED and the red Error        LEDs begin flashing.

9.

 Perform the installation test appropriate for your application.    

 See 

Installation Tests

 (pages 9-10).

Summary of Contents for GE Current WFA100-SN

Page 1: ...ices that provide On Off switching as well as 0 10V analog dimming control for ballasts and LED drivers The WFA100 SN also provides power and signal connections for low voltage occupancy sensors and p...

Page 2: ...in DCS wireless signals from the WAC to the WFA100 SN determine operation of the light s Design Caution Do not install a wireless adapter such as the WFA100 SN to control an electrical circuit that p...

Page 3: ...FA100 SN 3 Figure 4 Dimming Ballasts Figure 5 On Off non dimming Ballasts Perform Installation Test Suite 1 Perform Installation Test Suite 1 3 Wiring Continued Remove the jumper from the violet and g...

Page 4: ...On Off switching of ballasts and provides an occupancy sensor input Set the occupancy sensor for the minimum time delay This configuration allows the WFA100 SN to provide automatic 0 10V dimming contr...

Page 5: ...On Off It also provides an analog photosensor input 0 10V Remove the jumper from the violet and gray terminals before connecting the 0 10V dimming control wires This configuration allows the WFA100 SN...

Page 6: ...rcuit Regular power is brought into the fixture from an adjacent fixture and connects to the RRU X UM While Regular power is supplied to the RRU X UM the WFA100 SN provides switched On Off power to th...

Page 7: ...e ballast The WFA100 SN also controls dimming to the Regular Fixture and the Emergency Fixture The Emergency Fixture is powered by the Emergency power circuit The 0 10V dimming circuit from the WFA100...

Page 8: ...control device at the time of installation Finding installation issues or device problems earlier saves significant time during the commissioning process Record IEEE Addresses If you have not already...

Page 9: ...tosensor 1 Press and immediately release the Reset button The red Error LED flashes once then pauses and repeats 2 Check that the connected lights cycle On and Off or cycle from maximum to minimum bri...

Page 10: ...ray terminals If connected to an occupancy sensor remove the jumper from the Blue and Gray terminals If not connected to an occupancy sensor be sure the jumper is connected between the Blue and Gray t...

Page 11: ...hould particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to GE Current a Daintree company Questions Web products gecurrent com Phon...

Reviews: