Installation Guide

Daintree

®

 Networked Wireless Thermostat (WTS10)

2

1

Installation Process Continued

2

Wiring: Thermostat Terminals

3

Testing

7.  

On the thermostat body, locate switch SW1 on the circuit  

 

 

board as shown below. This is used to set the thermostat for    

 

operation with the HVAC system.

To prevent electrical shorts and potential damage to the 

thermostat, ensure all of the base wire connections are secure 

and are not touching any other terminal. Push any excess wire 

back into the wall cavity and insulate the wire opening with 

suitable material.

8. 

Set switches as appropriate for your system:

9

.   Attach the thermostat front body to the base, being

 

careful to align the terminal pins on the front body with

 

the terminal block on the base.

10

.  Restore system power.

11

.  Test the thermostat according to the procedure in the

 Test

 section for the connected HVAC system.

12

.  Set the time and date on the thermostat. See the

 

“Keypad Operation Guide.”

13

.  Review the default program schedules in the 

“Keypad

 

Operation Guide” 

and adjust as necessary.

14

.  When you are ready to commission the wireless network, 

 see 

Joining the ZigBee Wireless Network.

 System 

  Type 

Source 

Switch #1 

Switch#2

Conventional

Heat Pump

Electric
Gas

Heat 

Changeover

Valve

Cool 

Changeover

Valve

E/B (on, up)

G/O (off, down)

E/B (on, up)

G/O (off, down)

STD (on, up)

HP (off, down)

READ BEFORE TESTING 

•  Do not short across terminals on the gas valve or at the heating 

  or cooling system control board to test the thermostat installation. 

  This could damage the thermostat and void the warranty.

•  Do not select COOL mode if the outside temperature is below 

  50° F (10° C). This could damage the controlled cooling system and  

  cause personal injury. 

•  Ensure the power supply is correct and the display is reading 

  current room temperature.

WARNING

Summary of Contents for WTS10

Page 1: ... Installer Circle the type of equipment and give this information to the commissioning agent A 1 Stage Heat 1 Stage Cool Conventional System B 2 Stage Heat 2 Stage Cool Conventional System C 3 Stage Heat 2 Stage Cool Conventional System D 1 Stage Heat 1 Stage Cool Heat Pump System with out Auxiliary Heating E 2 Stage Heat 1 Stage Cool Heat Pump System with Auxiliary Heating F 2 Stage Heat 2 Stage ...

Page 2: ...stat according to the procedure in the Test section for the connected HVAC system 12 Set the time and date on the thermostat See the Keypad Operation Guide 13 Review the default program schedules in the Keypad Operation Guide and adjust as necessary 14 When you are ready to commission the wireless network see Joining the ZigBee Wireless Network System Type Source Switch 1 Switch 2 Conventional Hea...

Page 3: ...switch positions 3 The setting for STAGE is highlighted Press the button to scroll through the selections 1H1C or 2H 1C and 2H2C or 3H2C When the desired STAGE selection is highlighted press the DOWN button to enter your selection and advance to the FAN selection 4 Press the button to toggle the FAN output ON OFF Keep the FAN output ON while testing the other outputs 5 Press the DOWN button to hig...

Page 4: ...tion 1 F 1 C Measurements Setting range 45 F 90 F 7 0 C 32 0 C Setting resolution 1 F 0 5 C Accuracy 1 F 75 F Switching differential 1st stage User selectable 0 5 F default 1 0 F 2 0 F 0 25 C 0 5 C 1 0 C Switching differential 2nd stage Fixed 2 F 1 C Switching differential 3rd stage Control Fixed 2 F 1 C Operational differential Less than 2 F Control timing Compressor short cycle timer 5 min Resid...

Reviews: