Procedure 

1.

Clean threaded surfaces and pour locations

 should be with soap and water and

 

thoroughly dried before proceeding.

2.

Install two conduit runs

 (one signal, one power) between the enclosure I/O casting

 

and AC power source (located in a safe area or in an explosion-proof box). See

 

drawing P011 for added details.

3.

Shake the sealing compound powder

 well before mixing with water. The

 

recommended mix ratio is 5 parts powder to 1-part clean water, by weight.

4.

Place 25ml of 70°F water into a clean mixing container

 and gradually add powder to

 

water while mixing with a slow-speed mixer or by hand with a spatula until a uniform

 

consistency is obtained.

A minimum amount of water should be used. Excessive water reduces

 

mechanical strength, increases shrinkage, and delays set time.

Failure of the cement to adhere indicates setting has begun. Do not attempt to

 

re-temper by adding more water. Discard cement and start a new batch.

5.

Apply compound

 by pouring, casting, or using a mechanical dispenser. The sealing

 

compound hardens with an internal chemical-setting action in 18 to 24 hours at

 

ambient temperature. Working time of the sealing compound when the powder is

 

mixed with water is approximately 30 minutes at 70

°

F. If accelerated curing is

 

desired, low temperature oven drying at 180

°

F can be used. Do not expose the

 

sealing compound to higher temperatures, constant water immersion, or steam

 

environments while curing. If high humidity resistance is required in the cured

 

product, a moisture-resistant lacquer or silicone coating should be applied to the

 

exposed surfaces.

6.

Place Packing fiber around the ends

 of each individual wire or cable ends to create a

 

dam for pouring the compound into the PAC Seal. This allows for the entire contents

 

of the PAK Seal to be encapsulated by the compound with environmentally safe, 

non-asbestos material. 

7.

LUBT-2 lubricant is recommended for use on threaded joints.

 This lubricant is used

 

to prevent galling of the pipe threads when threading into couplings, junction boxes,

 

etc. It provides for undamaged male and female threads and a quick release when

 

parts are being disassembled. The thread lubricant should be a high-quality lubricant

 

used in temperatures ranging from -40

°

 to +50

°

 F, and is recommended for use in

 

hazardous locations. The PAC Seal Compound, packing fiber and LUBT-2 are available

 

from Killark at 

http://www.killark.com/

.

8.

For enhanced reliability

 of the Purge unit, an AC line conditioner is recommended.

 

AC power lines should be no smaller than 14 gauge and have a TRUE EARTH

 

GROUND.

Summary of Contents for 9016 X-Purge

Page 1: ...February 2022 D010 000002 Model 9016 X Purge User Manual...

Page 2: ...te radio frequency energy and if not installed and used in accordance with the instructions in this manual may cause interference to radio communications Such equipment has been tested and found to co...

Page 3: ...articular purpose or other warranty of quality whether expressed or implied except of title and against patent infringement Correction of nonconformities in the manner and for the period of time provi...

Page 4: ...d conduit entry 9016 15 18 enclosures 19 P008 X Purge front panel item location 20 P011 Cable and conduit entry 9016 mounted to enclosure 21 E030 Electrical input connections 22 M015 9016 X Purge dime...

Page 5: ...Division 1 hazardous areas The installation of an X Purge system on an enclosure in a Division 1 area renders the area within the enclosure to an essentially non rated environment Thus normally rated...

Page 6: ...ne see drawing P007 3 INPORTANT Bleed the pressurized purge air or inert gas line ensuring that any dirt moisture and contaminants are cleared from the line before connecting the pressurized purge air...

Page 7: ...This change may vary slightly on some units if in later testing the unit fails with an 3 2 over flow error code decrease the inlet pressure by another 2 PSI Note Pressure for use during start up 13 Re...

Page 8: ...dry location at 70 F Any equipment accidentally splashed with sealing compound should be cleaned with soap and water before the sealing compound cures Equipment Required Four PAC Seal fittings 1 NPT...

Page 9: ...f the sealing compound when the powder is mixed with water is approximately 30 minutes at 70 F If accelerated curing is desired low temperature oven drying at 180 F can be used Do not expose the seali...

Page 10: ...t gas line see drawing P011 3 Bleed the purge air or inert gas line to ensure that dirt moisture and other contaminants are cleared from the line prior to connecting the line to the unit 4 Connect the...

Page 11: ...pleted successfully and the same results were seen up to this point in the procedure you may skip the remaining steps of this procedure If not continue to Step Error Reference source not found 7 Slowl...

Page 12: ...uire the purge system be SHUT DOWN before correcting the problem and restarting the purge cycle Table 6 1 X Purge Status Light Key Color Code Meaning Status Recommended Action Green 0 Operate purge co...

Page 13: ...ooting Section page 15 Red 4 2 Faulty flow sensor Fatal Purge System component failure Contact DAISY Customer Service See Section 7 Review Customer Service on page 14 Red 4 3 Short purge switch is stu...

Page 14: ...ntact Daisy s Customer Service Department Equipment returned to DAISY for service must be accompanied by a valid Return Merchandise Authorization RMA number Anything shipped to DAISY without a valid R...

Page 15: ...restrictions and that the supply line is not kinked Restrictions in main purge line inside enclosure Ensure that the main purge line terminating in a brass tee fitting is not kinked or disconnected Le...

Page 16: ...th W 5 0 Depth D 5 lbs ENVIRONMENTAL Operating Temperature 32 122 F Storage Temperature 32 158 F Relative Humidity 10 95 Non condensing ELECTRICAL Power Usage 5 watts maximum Switching Capacity power...

Page 17: ...rge front panel item location 26 P013 X Purge back panel item location 27 P014 Stand alone X Purge pneumatic block diagram 28 E028 Stand alone X Purged electrical block diagram 29 E017 Power interface...

Page 18: ...Model 9016 X Purge Operator Interface Daisy Data Displays Inc February 2022 18 D010 000002 THIS PAGE INTENTIONALLY BLANK...

Page 19: ...Page 19...

Page 20: ...Page 20...

Page 21: ...Page 21...

Page 22: ...Page 22...

Page 23: ...Page 23...

Page 24: ...Page 24...

Page 25: ...Page 25...

Page 26: ...Page 26...

Page 27: ...Page 27...

Page 28: ...Page 28...

Page 29: ...Page 29...

Page 30: ...Page 30...

Page 31: ...3 10 WHITE BLUE 10 3 J9 3 3 4 9 BLUE WHITE 9 4 J9 4 4 5 8 WHITE GREEN 8 5 J9 5 5 6 7 GREEN WHITE 7 6 J9 6 6 7 6 WHITE ORANGE 6 7 J9 7 7 8 5 ORANGE WHITE 5 8 J9 8 8 9 4 ORANGE RED 4 9 J9 9 9 10 3 RED O...

Page 32: ......

Page 33: ......

Page 34: ...Page 34...

Page 35: ...Page 35...

Page 36: ...Page 36...

Page 37: ...Page 37...

Page 38: ...Page 38...

Page 39: ...Page 39...

Reviews: