Trouble-shooting Guide 

8.2 Division 1 Z-Purge Troubleshooting 

PROBLEM 

POSSIBLE CAUSE 

SUGGESTED SOLUTION 

The flow cannot be adjusted up to 

150 SCFH during purge 

Improper flow meter reading 

For correct operation, the purge 

unit must be mounted vertically so 

that the flow meter is vertically 

plumb 

Improper regulator adjustment 

Adjust the air inlet regulator to 

increase air supply 

The purge control is not set to 

purge 

Check the position of the control 

valve to ensure that it is set to 

“Purge” 

Insufficient air supply 

Check your purge gas supply to 

ensure that it can supply 150 SCFH. 

If you cannot achieve 150 SCFH, 

then purge times must be 

recalculated. Contact DAISY 

customer service for assistance. 

Restrictions in the air supply line 

Check your air supply line for 

blockages and kinks 

Contamination in the air supply 

Ensure that the purge gas supply is 

clean, dry, and free of oil – a 

water/oil separator should be 

installed near the connection to the 

purge control 

Restrictions in the purge line from 

the purge control into the 

enclosure 

Ensure that the purge line from the 

purge control into the enclosure is 

not kinked, has no internal 

obstructions, and is unrestricted at 

its open end (at least 0.5” from any 

object in the path of the air flow) 

During operation (control valve set 

to “Operate”), the internal 

pressure does not reach/will not 

maintain 1” of water column 

The enclosure is not sealed and is 

leaking 

Ensure that all access doors are 

closed and latched. Ensure that all 

access panels are closed and sealed. 

Make sure no unsealed holes or 

openings are present in the 

enclosure. 

Insufficient air flow 

Adjust the regulator on the purge 

control to increase the air flow 

Pack-Seals are not poured 

Pack-Seals must be poured in 

conduits entering the enclosure to 

prevent air from escaping via the 

conduit entry. Ensure that this has 

been done. 

Exhaust control valve setting 

incorrect 

Adjust the purge control exhaust 

valve for a higher internal pressure. 

It may take several minutes for 

adjustments to this setting to take 

effect. 

Summary of Contents for 9017

Page 1: ...February 2022 Model 9017 Y Z Purge User Manual...

Page 2: ...requency energy and if not installed and used in accordance with the instructions in this manual may cause interference to radio communications Such equipment has been tested and found to comply with...

Page 3: ...purpose or other warranty of quality whether expressed or implied except of title and against patent infringement Correction of nonconformities in the manner and for the period of time provided above...

Page 4: ...Operation 9 5 1 Division 1 Y Z Purge Start Up Operation 9 6 Operation Notes 10 6 1 Division 1 Z Purge 10 7 1 Y Z Purge Ext Relay Kit Model 9121 12 7 1 1 Purge Types 12 7 1 2 General Y Z Purge Operati...

Page 5: ...ts This manual describes the general procedures for installing and operating DAISY Model 9017 Y Z Purge systems The text portion of the manual also includes an overview of the theory behind the method...

Page 6: ...assed through a given enclosure eliminate any possible flammable concentration of substances within the enclosure the minimum of four volumes of exchange still applies Factory Mutual Class Number 3620...

Page 7: ...eed the purge air or inert gas line to insure that dirt moisture and other contaminants are cleared from the line prior to connecting the line to the unit 5 Connect the purge gas line to the inlet of...

Page 8: ...should be illuminated green If not check the internal pressure it should be between 0 4 and 10 0 of Water Column The pressure good led must be illuminated green at this time If it is not please consu...

Page 9: ...om other conduits to prevent radiated or induced interference Devices that produce spikes surges and brownouts are detrimental to computers and can corrupt data and interfere with purging systems Do n...

Page 10: ...s 1 NPT or 0 75 NPT for the Z Purge or sealing conduits The PAC Seal and conduit size selected will depend on the size and number of conductors which must be run to the unit Check the NEC tables Chapt...

Page 11: ...F If accelerated curing is desired low temperature oven drying at 180 F can be used Do not expose the sealing compound to higher temperatures constant water immersion or steam environments while curi...

Page 12: ...separator or filter capable of supplying 150 SCFH at 20 100 PSI Fittings and tubing for purge air or inert gas supply 0 25 NPT Male to connect to the inlet of the purge system Local air pressure shut...

Page 13: ...lve to PURGE Make sure that the Flow Meter reads 150 SCFH If not readjust the regulator for 150 SCFH 6 The size of your enclosure will determine the purge time unless you purchased a Y Z Purge on a DA...

Page 14: ...in the red zone below 1 of water column the operator should immediately disconnect power and signal connections to the unit using switches in a safe area DAISY s Z purge systems are also equipped wit...

Page 15: ...ntact Daisy s customer service department Equipment returned to DAISY for service must be accompanied by a valid return merchandise authorization RMA number Anything shipped to DAISY without a valid R...

Page 16: ...the event of a loss of pressure within the enclosure the alarm system will indicate a failure The operator must then manually shut off power and signal connections at a safe disconnect location 7 1 3...

Page 17: ...Daisy Data Displays Inc February 2022 13 D011 000002 7 1 5 Model 9121 Block Diagram IMPORTANT The Model 9121 Relay Kit DOES NOT POWER DOWN THE ALARM CIRCUIT IN THE CABINET POWER TO THE PROTECTED EQUI...

Page 18: ...and free of oil a water oil separator should be installed near the connection to the purge control Restrictions in the purge line from the purge control into the enclosure Ensure that the purge line...

Page 19: ...plied to the enclosure after the internal pressure has reached 1 of water column or higher and when the full purge time has elapsed Insufficient internal pressure The pressure within the enclosure mus...

Page 20: ...W x 2 75 D 9 pounds Interface Box 7 25 H x 12 25 W x 3 50 D 5 pounds See drawing M012 for dimensions Environmental Operating Temperature 0 50 C Storage Temperature 0 70 C Relative Humidity 10 100 RH N...

Page 21: ...Number Description Page P015 Z Purge Cable Conduit Entry 18 M014 Z Purge Dimensions 19 M012 Z Purge Mounting 20 M017 Z Purge Mounting Options 21 P016 Z Purge Block Diagram 22 P017 Z Purge Front Panel...

Page 22: ...SIONS ARE IN INCHES Daisy Data Inc THIS DOCUMENT IS PROPRIETARY TO DAISY DATA INC THE USE OF OR REPRODUCTION OF THIS DOCUMENT IS PROHIBITED EXCEPT AS AUTHORIZED BY 2850 Lewisberry Road York Haven PA 1...

Page 23: ...Page 19 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...

Page 24: ...Page 20 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...

Page 25: ...Page 21 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...

Page 26: ...Page 22 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...

Page 27: ...Page 23 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...

Page 28: ...Page 24 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...

Page 29: ...Model 9017 Y Z Purge Operator Interface Daisy Data Displays Inc Page 25...

Page 30: ...Model 9017 Y Z Purge Operator Interface Daisy Data Displays Inc Page 26...

Page 31: ...Model 9017 Y Z Purge Operator Interface Daisy Data Displays Inc Page 27...

Reviews: