Model 9017 Y/Z-Purge Operator Interface
Daisy Data Displays, Inc.
February 2022
15
D011-000002
PROBLEM
POSSIBLE CAUSE
SUGGESTED SOLUTION
Restrictions in the air connections
Ensure that the air connection at
the regulator is not kinked, has no
obstructions, and is firmly
connected.
The “Pressure Good” indicator
does not light when the unit is
powered
Incorrect power-up sequence
Power should only be applied to the
enclosure
after
the internal
pressure has reached 1” of water
column or higher and when the full
purge time has elapsed
Insufficient internal pressure
The pressure within the enclosure
must be within the operating (or
“safe”) range. If you are having
trouble maintaining a suitable
pressure, see the previous section
of this trouble-shooting guide.
Alarm board is not receiving
power
Ensure that AC power has been
connected to the unit, and that the
power is turned on
Voltage is set incorrectly
Ensure that the 120/240 VAC switch
on the alarm board is set
appropriately for your power source
Summary of Contents for 9017
Page 1: ...February 2022 Model 9017 Y Z Purge User Manual...
Page 23: ...Page 19 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...
Page 24: ...Page 20 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...
Page 25: ...Page 21 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...
Page 26: ...Page 22 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...
Page 27: ...Page 23 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...
Page 28: ...Page 24 Daisy Data Displays Inc Model 9017 Y Z Purge Operator Interface...
Page 29: ...Model 9017 Y Z Purge Operator Interface Daisy Data Displays Inc Page 25...
Page 30: ...Model 9017 Y Z Purge Operator Interface Daisy Data Displays Inc Page 26...
Page 31: ...Model 9017 Y Z Purge Operator Interface Daisy Data Displays Inc Page 27...