Installation and Maintenance

Service Manual

Do not install the outdoor unit in pits or air vents

Installing the pipes

 Use suitable connecting pipes and equipment for

 the refrigerant R410A.

Models(m)

14/18K

21/24K

28K

Max. connection pipe length 

20

60

70

Max. connection pipe 

length(Simpleone indoor unit)

10

20

20

The sum of the capacity codes of the indoor units should be among 50%-

150% of that of the outdoor unit.

 Wrap all the refrigerant pipes and joints.

Caution: Installation Must be Performed in Accordance with the NEC/

CEC by Authorized Personnel Only.

Humid air left inside the refrigerant circuit can cause compressor 

malfunction. After having connected the indoor and outdoor units, bleed 

the air and humidity from the refrigerant circuit using a vacuum pump.

(1) Unscrew and remove the caps from the 2-way and 3-way valves.

(2) Unscrew and remove the cap from the service valve.

(3) Connect the vacuum pump hose to the service valve.

(4) Operate the vacuum pump for 10-15 minutes until an absolute vacuum

of 10 mm Hg has been reached.

(5) With the vacuum pump still in operation, close the low-pressure knob

on the vacuum pump coupling. Stop the vacuum pump.

(6) Open the 2-way valve by 1/4 turn and then close it after 10 seconds.

Check all the joints for leaks using liquid soap or an electronic leak device.

(7) Turn the body of the 2-way and 3-way valves. Disconnect

the vacuum pump hose.

(8) Replace and tighten all the caps on the valves.

Diameter (mm)

Twisting moment (N.m)

ĭ

15-20

ĭ

35-40

ĭ

60-65

ĭ

45-50

ĭ

70-75

,IWKHVSHFL¿FDWLRQRIRXWGRRUXQLWJDVYDOYHLVEXWFXUVWRPHUQHHGV

to install 1/2"indoor unit so that it is need to use a “pipe joint subassembly” 

(Code 06643008) to make a conversion joint with outdoor unit gas valve 

and connection pipe, as show in following.

Installing the Outdoor Unit

Use bolts to secure the unit to a flat, solid floor. 

When mounting the unit on a wall or the roof, make

sure the support is firmly secured so that it cannot

move in the event of intense vibrations or a strong 

wind.

Do not install the outdoor unit in pits or air vents
Use suitable connecting pipes and equipment for the 

refrigerant R410A.

Wrap all the refrigerant pipes and joints.

Tighten the connections using two wrenches working 

in opposite directions.

Humid air left inside the refrigerant 

circuit can cause com-

pressor malfunction. After having connected the indoor 

and outdoor units, bleed the air and humidity from the 

refrigerant circuit using a vacuum pump.

1.Unscrew and remove the caps from the 2-way and 3-

way valves.

2.Unscrew and remove the cap from the service valve.

3.Connect the vacuum pump hose to the service valve.

4.Operate the vacuum pump for 10-15 minutes until an

absolute vacuum of 10 mm Hg has been reached.

5.With the vacuum pump still in operation, close the 

low-pressure knob on the vacuum pump coupling. Stop

the vacuum pump.

6.Open the 2-way valve by 1/4 turn and then close it

after 10 seconds

.

 Check all the joints for leaks using 

liquid soap or an electronic leak device.

7.Turn the body of the 2-way and 3-way valves. Discon-

nect the vacuum pump hose.

8.Replace and tighten all the caps on the valves.

INDOOR

UNIT

Install the drain fitting and the drain hose(for

model with heat pump only)

Condensation is produced and flows from the outdoor unit

when the appliance is operating in the heating mode. In order

not to disturb neighbours and to respect the environment, 

install a drain fitting and a drain hose to channel the conden-

sate water. Install the drain fitting and rubber washer on the 

outdoor unit chassis and connect a drain hose to it as shown 

in the figure.

Vacuum pump

Vacuum pump

Vacuum pump

Connect to the

indoor unit

Twisting moment (N.m)

Diameter (mm)

14-18N m(140-180kgf.cm)

18K unit need to be installed the indoor unit

conversion joint

Caution: Installation Must be Performed in Accordance

with the NEC/CEC by Authorized Personnel Only.

(8) Secure

18K Model:

Installing the pipes

36.35(1/4”)

39.52(3/8”)

312.7(1/2”)

2-way valve

Refrigerant fluid direction of flow

3-way valve

Service

 inlet

(8) Secure

Valve cap

Valve cap

(2) Turn

(2) Turn

(2) Turn

(8) Secure

(7) Turn to open fully

(7) Turn to open fully

(6) Open by 1/4 turn

Models(m) 14/18K GWHD(24)NK3DO 24/28K

Max. connection

pipe length

20

20

70

Max. connection

pipe length(Simple

one indoorunit) 10

10

20

The refrigerant pipes must not exceed the maximum

heights

 10m. 

34-42N m(340-420kgf.cm)

49-61N m(490-610kgf.cm)

conversion joint

,QVWDOOWKHGUDLQ¿WWLQJDQGWKHGUDLQKRVHIRUPRGHOZLWK

heat pump only)

Condensation  is  produced  and  flows  from  the  outdoor  unit 
when the appliance is operating in the heating mode. In order
not  to  disturb  neighbours  and  to  respect  the  environment, 
install  a  drain  fitting  and  a  drain  hose  to  channel  the 

FRQGHQVDWHZDWHU,QVWDOOWKHGUDLQ¿WWLQJDQGUXEEHUZDVKHU

on the outdoor unit chassis and connect a drain hose to it as 

VKRZQLQWKH¿JXUH

When mounting the unit on a wall or the roof, make sure the 

VXSSRUWLV¿UPO\VHFXUHGVRWKDWLWFDQQRWPRYHLQWKHHYHQWRI

intense vibrations or a strong wind.

The refrigerant pipes must not exceed the maximum heights

m(14K&18K &24Kx2)or 10m(24Kx3&28K).

Tighten the connections using two wrenches working in opposite 

directions.by Authorized Personnel Only.

Summary of Contents for DS-9KIDB

Page 1: ...Service Manual Models ASD9U2I DN ASD912UI DN...

Page 2: ...5U1 Throttling Method Electron expansion valve Cooling Operation Ambient Temperature Range O C 18 43 Heating Operation Ambient Temperature Range O C 15 24 Condenser Material Aluminum Fin copper Tube C...

Page 3: ...Additional Gas Connection Pipe Length m 10 10 Connection Pipe Gas Additional Charge g m 20 20 Outer Diameter of Liquid Pipe GREE Allocation Metric mm Outer Diameter of Gas Pipe GREE Allocation Metric...

Page 4: ...6 m3 K 550 500 430 300 550 480 410 290 HKXPLGLI LQJ 9ROXPH K 0 8 1 4 Indoor Unit Model of Indoor Unit 6 6 3URGXFW RGH RI QGRRU 8QLW DQ 7 SH URVV RZ URVV RZ LDPHWHU HQJWK mm DQ 0RWRU RROLQJ 6SHHG 6 0...

Page 5: ...Technical Information Service Manual Outline Dimension Diagram Indoor Unit Unit mm Models W H D W1 W2 W3 09 12K 773 250 185 131 462 180 D H W 75 35 55 W3 W2 W1 55 35 75...

Page 6: ...anual 3 Outline Dimension Diagram 892 341 396 963 560 700 368 Unit mm 12 Technical Information Service Manual 3 Outline Dimension Diagram 892 341 396 963 560 700 368 Unit mm 12 Technical Information 8...

Page 7: ...ease refer to the actual models This is a general use remote controller it could be used for the air conditioners with multifunction For some function which the model doesn t have if press the corresp...

Page 8: ...m AUTO COOL DRY FAN and HEAT as the following AUTO COOL DRY FAN HEAT Note Only for models with heating function This button is used for setting Fan Speed in the sequence that goes from AUTO to then ba...

Page 9: ...d buttons simultaneously 3s to lock or unlock the keypad If the remote pressing any button blinks three times controller is locked is displayed In this case Combination of and buttons About lock About...

Page 10: ...me models Replacement of batteries in remote controller Emergency operation If remote controller is lost or damaged please use auxiliary button to turn on or turn off the air conditioner When the air...

Page 11: ...t adequately grounded The grounding wire can t be used for other purposes 6 Must apply protective accessories such as protective boards cable cross loop and wire clip 7 The live wire neutral wire and...

Page 12: ...tape 4 Electroprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 Tor...

Page 13: ...e the bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installation Note th...

Page 14: ...o the wall At least 250cm At least 15cm At least 300cm Space to the obstruction Space to the ceiling Space to the obstruction At least 15cm At least 15cm Space to the wall Space to the wall At least 2...

Page 15: ...LW SOHDVH QRWH WKH IROORZLQJ WDEOH LU VZLWFK VKRXOG EH LQFOXGHG PDJQHW EXFNOH DQG KHDWLQJ EXFNOH IXQFWLRQ LW FDQ SURWHFW WKH FLUFXLW VKRUW DQG RYHUORDG DXWLRQ SOHDVH GR QRW XVH WKH IXVH RQO IRU SURWHF...

Page 16: ...H SRVLWLRQ RI SLSLQJ KROH VKRXOG EH D OLWWOH ORZHU WKDQ WKH ZDOO PRXQWHG IUDPH V VKRZ LQ LJ 5 Connect the Pipe of Indoor Unit LP WKH SLSH MRLQW DW WKH FRUUHVSRQGLQJ EHOOPRXWK V VKRZ LQ LJ 3UHWLJKWHQLQ...

Page 17: ...QJ FRYHU DQG WKHQ WDNH GRZQ WKH FRYHU V VKRZ LQ LJ 8 Bind up Pipe LQG XS WKH FRQQHFWLRQ SLSH SRZHU FRUG DQG GUDLQ KRVH ZLWK WKH EDQG V VKRZ LQ LJ 5HVHUYH D FHUWDLQ OHQJWK RI GUDLQ KRVH DQG SRZHU FRUG...

Page 18: ...apacity please note the following table Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Caution please do not use the fuse only fo...

Page 19: ...d 3 way valves 2 Unscrew and remove the cap from the service valve 3 Connect the vacuum pump hose to the service valve 4 Operate the vacuum pump for 10 15 minutes until an absolute vacuum of 10 mm Hg...

Page 20: ...NLQJ XS DQG PRYLQJ WKH XQLWV RX PXVW EH JXLGHGE WUDLQHG DQG TXDOL HG SHUVRQ Ensure that the recommende dspace is left around the appliance 30cm Space to the cover or above 30cm 50cm Air inlet side or...

Page 21: ......

Reviews: