Page 20 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
C.
Control
Specifications
C.1.
SK
‐
NCFMCD
‐
001
Complete
function
FCU
Controller
Used
in
all
High
‐
Wall
[V]
~S
unit
configurations.
Complete
function
integrated
controller,
compatible
with
IR
handset
controller,
wired
wall
‐
pad,
serial
networking
for
master
‐
slave
and
MODBUS
applications.
C.1.1.
Abbreviations
Ts
=
Setting
temperature
Tr
=
Room
air
temperature
Ti1
=
Chilled
water
coil
temperature
Ti2
=
Hot
water
coil
temperature
AUX1
=
Hot
water
free
contact
AUX2
=
Chilled
water
free
contact
MTV1
=
Chilled
Motorized
valve
MTV2
=
Hot
Motorized
valve
C.1.2.
Definition
of
Input/Output
I/O
Code
2
‐
Pipe
4
‐
Pipe
Analogue
Input
Return
air
sensor
AI1
Return
air
temperature
(Tr)
2
‐
pipe
coil
circuit
sensor
AI2
Chilled
/
hot
water
coil
circuit
(Ti1)
Chilled
water
coil
circuit
(Ti1)
Hot
water
sensor
AI3
N/A
Hot
water
coil
circuit
(Ti2)
Input
LED
display
/
IR
receiver
X
‐
DIS1
Digital
communication
port
to
LED
display
/
IR
receiver
board.
Wired
wall
pad
TTL1
Digital
communication
port
to
wired
wall
pad
board.
Digital
input
Occupancy
contact
On/Off
Window
contacts:
For
remote
ON/OFF
(when
DIPB
SW1
=
1).
Economy
contacts:
For
remote
activation
of
economy
mode
(when
DIPB
SW1
=
0).
Electrical
heater
safety
switch
EH
Voltage
‐
free
(NC).
The
contact
is
closed
before
the
EH
is
turned
on.
Power
input
Phase
L1
Power
supply
to
the
PCB
and
all
the
loads
connected
to
the
voltage
outputs.
Max
length:
5
m.
Neutral
N1
Power
supply
to
the
PCB
and
all
the
loads
connected
to
the
voltage
outputs.
Max
length:
5
m.
Earth
PE1
Power
supply
to
the
PCB
and
all
the
loads
connected
to
the
voltage
outputs.
Max
length:
5
m.
Voltage
output
Fan
CN4
Fan
driver
Valve
1
MTV1
2
‐
pipe
coil
circuit
valve
output
–
chilled
/
hot
water
valve.
Voltage
output
(L)
4
‐
pipe
coil
circuit
valve
output
–
chilled
water
valve.
Voltage
output
(L)
Valve
2
MTV2
Reserved
4
‐
pipe
coil
circuit
valve
output
–
hot
water
valve.
Voltage
output
(L)
Voltage
of
electrical
heater
(Live)
HEAT
Voltage
output
(L),
maximum
25
A
Output
Stepping
motor
CN1
/
CN2
Louver
stepping
motor
relay
Auxiliary
contact
2
AUX2
Cooling
mode
signal
relay
(NO).
Voltage
free
contact.
To
ensure
the
sensitivity
of
the
connection,
please
make
sure
max
wiring
length
<
5
m,
5
A
Auxiliary
contact
1
AUX1
Heating
mode
signal
switch
(NO).
Voltage
free
contact.
To
ensure
the
sensitivity
of
the
connection,
please
make
sure
max
wiring
length
<
5
m.
5
A
Serial
BUS
port
CN3
Master
‐
slave
network
serial
connection
OR
MODBUS
/
local
PC
host
network
serial
connection.
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...