Page 25 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
With
Electrical
Heater
as
Primary
Heat
Source
a)
MTV1,
MTV2
,
and
AUX2
are
always
off.
b)
If
Ti2
≤
30ºC
(or
Ti2
is
damaged
or
not
connected),
1)
If
Tr
≤
Ts
﹣
1ºC
(or
–
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
the
electrical
heater
and
AUX1
are
turned
on.
Indoor
fan
runs
at
set
speed.
2)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
the
electrical
heater
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200RPM.
a)
If
Ti2
>
30ºC,
MTV2
and
AUX2
are
off.
1)
If
Tr
≤
Ts
﹣
1ºC
(or
–
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
the
electrical
heater
is
turned
off
while
MTV1
and
AUX1
are
turned
on.
Indoor
fan
runs
at
set
speed.
2)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV1
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200RPM.
d)
The
range
of
Ts
is
16
‐
30ºC.
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
PRE
‐
HEAT
Without
Electrical
Heater
a)
If
Ti1
<
36ºC
[or
<
28ºC
is
selected
by
DIPB
‐
S2
position
SW4],
then
MTV1
and
AUX1
are
turned
on,
indoor
fan
runs
at
200rpm.
b)
If
Ti1
≥
38ºC
[or
≥
30ºC
is
selected
by
DIPB
‐
S2
position
SW4],
then
MTV1
and
AUX1
are
turned
on,
indoor
fan
runs
at
set
speed.
c)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
pre
‐
heat
time
is
set
for
2
minutes.
Indoor
fan
runs
at
set
speed.
With
Electrical
Heater
a)
If
the
indoor
fan
speed
≥
300rpm,
then
the
electrical
heater
will
turn
on.
POST
‐
HEAT
Without
Electrical
Heater
a)
If
Ti1
≥
38ºC,
then
MTV1
and
AUX
1
are
off,
then
indoor
fan
continues
to
run
at
set
speed.
b)
If
36ºC
≤
Ti1
≤
38ºC,
then
MTV1
and
AUX1
are
turned
off.
Then
indoor
fan
maintains
its
original
state.
c)
If
Ti1
<
36ºC,
then
MTV1
and
AUX1
are
turned
off.
Then
indoor
fan
runs
at
200rpm.
d)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
post
‐
heat
time
is
set
for
3
minutes.
Indoor
fan
runs
at
set
speed.
With
Electrical
Heater
a)
Indoor
fan
will
run
at
200rpm
before
the
unit
turns
off
for
20
seconds.
OVER
‐
HEAT
PROTECTION
OF
INDOOR
COIL
a)
If
Ti1
≥
75ºC,
then
MTV1
and
AUX1
are
turned
off.
Indoor
fan
remains
on
and
runs
at
high
speed.
b)
If
Ti1
<
70ºC,
then
MTV1
and
AUX1
are
turned
on.
Indoor
fan
remains
on
and
runs
at
set
speed.
c)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
protection
mode
will
be
overridden
and
the
unit
will
work
according
to
the
pre
‐
heat
and
post
‐
heat
program.
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...