Page 30 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
LOW
TEMPERATURE
PROTECTION
OF
INDOOR
COIL
a)
If
Ti1
≤
2ºC
for
2
minutes,
then
MTV1
and
AUX2
are
turned
off.
If
indoor
fan
is
set
for
low
speed,
then
it
will
run
at
medium
speed.
If
it
is
set
at
medium
or
high
speed,
then
it
will
keep
running
at
the
same
speed.
b)
If
Ti1
≥
5ºC
for
2
minutes,
then
MTV1
and
AUX2
are
turned
on.
Indoor
fan
runs
at
set
speed.
OVER
HEAT
PROTECTION
OF
INDOOR
COIL
a)
If
Ti2
≥
75ºC,
then
MTV2
and
AUX1
are
turned
off.
Indoor
fan
remains
on
and
runs
at
high
speed.
b)
If
Ti2
<
70ºC,
then
MTV2
and
AUX1
are
turned
on.
Indoor
fan
remains
on
and
runs
at
set
speed.
c)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
protection
mode
will
be
overridden
and
the
unit
will
work
according
to
the
pre
‐
heat
and
post
‐
heat
set
times.
DEHUMIDIFICATION
MODE
a)
MTV2,
AUX1
and
heater
are
always
off.
b)
If
Tr
≥
25ºC,
then
MTV1
and
AUX2
will
be
turned
on
for
3
minutes,
and
then
off
for
4
minutes.
c)
If
16ºC
≤
Tr
<
25ºC,
then
MTV1
and
AUX2
will
be
turned
on
for
3
minutes,
and
then
off
for
6
minutes.
d)
If
Tr
<16ºC,
then
MTV1
and
AUX2
will
be
turned
off
for
4
minutes.
e)
At
the
end
of
the
above
dehumidification
cycle,
the
system
will
decide
the
next
dehumidification
control
option.
Indoor
fan
will
run
at
low
speed
throughout
the
dehumidification
process.
AUTO
‐
MODE
a)
If
the
current
running
mode
is
AUTO
COOL
mode,
it
will
change
over
to
AUTO
HEAT
mode
upon
satisfying
all
the
conditions
below:
1)
Ts
–
Tr
≥
1°C
(or
–
4ºC
if
economy
contact
is
activated).
2)
MTV1
has
stopped
≥
10
minutes.
b)
If
the
current
running
mode
is
AUTO
HEAT
mode,
it
will
change
over
to
AUTO
COOL
mode
upon
satisfying
all
the
conditions
below:
1)
Tr
‐
Ts
≥
1°C
(or
+
4ºC
if
economy
contact
is
activated).
2)
MTV2
has
stopped
≥
10
minutes.
Note:
AUTO
COOL
or
AUTO
HEAT
operations
are
the
same
as
COOL
or
HEAT
mode
respectively.
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...