Page 41 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
4)
Reconnect
the
communication
plug
to
the
control
box
Using
Remote
Control
Handset
to
Set
Master
Control
Unit:
a)
Connect
all
the
units
PCBs
according
to
the
wire
color
and
type
of
connector.
b)
Select
the
master
unit
by
setting
DIPA
‐
S1
SW6
to
ON
(=1)
in
the
PCB.
c)
Ensure
the
DIPA
‐
S1
SW6
is
set
to
OFF
(=0)
in
the
PCB
on
each
slave
unit.
d)
Switch
on
the
units
by
connecting
the
main
power
supply.
e)
Using
the
handset
set
the
operation
parameters
for
the
master
unit
which
will
automatically
send
the
settings
to
the
slave
unit.
f)
Master
unit
will
beep
twice
confirming
receipt
of
commands
while
the
slave
unit
will
beep
once.
Using
Wall
pad
to
Set
Master
Control
Unit:
a)
Connect
all
the
units
PCBs
according
to
the
wire
color
and
type
of
connector.
b)
Select
the
master
unit
by
setting
DIPA
‐
S1
SW6
to
ON
(=1)
in
the
PCB.
c)
Ensure
the
DIPA
‐
S1
SW6
is
set
to
OFF
(=0)
in
the
PCB
on
each
slave
unit.
d)
Provide
each
slave
unit
with
an
addressable
code
by
configuring
SW1
–
SW5
of
DIPA
‐
S1
according
to
the
DIP
switch
setting
table.
e)
Switch
on
the
units
by
connecting
the
main
power
supply.
f)
Using
the
wall
pad
set
the
operation
parameters
for
the
master
unit
which
will
send
the
setting
to
the
slave
units
by
Global
‐
control
communication
or
Addressable
communication
methods.
g)
Master
unit
will
beep
twice
confirming
receipt
of
commands
while
the
slave
unit
will
beep
once.
MASTER
‐
SLAVE
CONTROL
The
control
PCB
can
receive
data
from
both
wireless
LCD
handset
and
wired
wall
pad.
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...