Page 47 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
C.4.5.
LED
Indication
For
all
units
Power
/
Operation
LED
light
(both
green)
Unit
on
Operation
LED On,
Power
LED
Off
Unit
in
standby
Power
LED On,
Operation
LED
Off
C.4.6.
Error
Description
For
all
units
‐
Operation
LED
light
(Green)
Item
Blink
Reason
Remedy
Indoor
coil
sensor
1
failure
Green
LED
blinks
4
times,
stops
for
3s
Ti1
sensor
connection
is
unplugged
or
damaged.
1.
Check
if
Ti1
plug
is
connected
or
not.
2.
Check
if
sensor’s
resistance
is
correct
or
not.
EC
motor
failure
Green
LED
blinks
9
times,
stops
for
3s
No
EC
motor
feedback
1.
Check
if
EC
motor’s
wires
are
connected.
2.
Check
the
EC
motor