003
C.5.
Open
Modbus
protocol
Transfer
Mode:
RTU,
BAUD
Rate:
9600bps,
8
data
bit,
1
stop
bit,
None
parity
bit
The
communications
require
a
delay
of
80ms
between
reading
an
answer
and
sending
the
next
command.
All
temperatures
are
equal
to
reading
data*10
accuracy:
0.1
degree
C.
Supported
Functions:
Function
Code
Function
Description
01(01H)
Read
Coils
02(02H)
Read
Discrete
Inputs
03(03H)
Read
Holding
Registers
04(04H)
Read
Input
Registers
05(05H)
Write
Single
Coil
06(06H)
Write
Single
Register
15(0FH)
Write
Multiple
Coils
16(10H)
Write
Multiple
Registers
255(FFH)
Extended
Commands
which
are used
to
test unit
Valid
Error
code
table:
Error
code
Description
Definition
01
(01H)
Invalid
commands
Received
commands
beyond
valid
commands
02
(02H)
Invalid
data
address
Data
addresses
beyond
valid
data
address
03
(03H)
Invalid
data
Data
beyond
definition
range
04
(04H)
Write
data
not
successful
Write
data
did not
succeed
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...