6.9 For Serviceman
24 Hz
54 MIN
65 MIN
10 MIN
OPERATION PARAMETER
1/6
OPERATE MODE
COOL
CURRENT 12 A
COMPRESSOR FREQUNCY
COMP. RUN TIME1
COMP. RUN TIME2
COMP. RUN TIME3
OPERATION PARAMETER
COMP.RUN TIME4
1000 HOUR
EXPANSION VALVE 240 P
FAN SPEED
IDU TARGET FREQUENCY
FREQUENCY LIMITED TYPE
T1 LEAVING WATER TEMP.
0 HZ
0
25 °C
600 R/MIN
T1B CIRCUIT2 WATER TEMP.
30 °C
30 °C
T2 PLATE F-OUT TEMP.
45 °C
T2B PLATE F-IN TEMP.
-7 °C
T3 OUTDOOR EXCHANGE TEMP.
-7 °C
T4 OUTDOOR AIR TEMP.
-7 °C
T5 WATER TANK TEMP.
3/6
OPERATION PARAMETER
Ta ROOM TEMP.
OPERATION PARAMETER
25 °C
P1 COMP. PRESSURE1
TW-O PLATE W-OUTLET TEMP.
TW-I PLATE W-INLET TEMP.
Th COMP. SUCTION TEMP.
Tp COMP. DISCHARGE TEMP.
T1S’ C1 CLI. CURVE TEMP.
T1S2’ C2 CLI. CURVE TEMP.
25 °C
25 °C
25 °C
25 °C
200 kPa
The power consumption parameter is
preparatory.
if some parameter not be activated in the
system, the parameter will show "--"
The heat pump capacity is for reference only, not
used to judge the ability of the unit. The accuracy
of sensor is ±1
℃
. The flow rates parameters are
calculated according to the pump running
parameters,the deviation is different at different flow
rates,the maximum of deviation is 15%.
INFORMATION
i
6.9.1 About For Serviceman
FOR SERVICEMAN is used for installater and service
engineer.
Setting the function of equipment.
Setting the parameters.
20
6.9.2 How To Go To For Serviceman
Go to ''MENU'' > ''FOR SERVICEMAN''. Press ''OK''.
The FOR SERVICEMAN is used for installer or service
engineer. It is NOT instended the home owener alters
setting with this menu.
It is for this reason password protection is requierd to
prevent unauthorised access to the service settings.
The password is 234.
PLEASE INPUT PASSWORD:
2
3 4
ENTER
OK
FOR SERVICEMAN
ADJUST
6.9.3 How To Exit For SERVICEMAN
Active the setting and exit?
NO
YES
CONFIRM
OK
FOR SERVICEMAN
If you have set all the parameter.
Press ''BACK'', the following page will appear
:
Select ''YES'' and press ''OK'' to exit the FOR
SERVICEMAN.
After exiting the FOR SERVICEMAN, the unit will be
turned off.
2/6
4/6
OPERATION PARAMETER
25 °C
DC GENERATRIX VOLTAGE
DC GENERATRIX CURRENT
WATER FLOW
HEAT PUMP CAPACTIY
HMI SOFTWARE
IDU SOFTWARE
ODU SOFTWARE
SUPPLY VOLTAGE
POWER CONSUM.
TF MODULE TEMP.
230 V
1000 KWh
25 °C
55 °C
420 V
5/6
OPERATION PARAMETER
18 A
00-00-2000V00
00-00-2000V00
00-00-2000V00
1.72 M3/H
11.52 KW
6/6
ADJUST