INSTALLATION
•
Take your UPS out of its packing.
•
Make sure the mains supply voltage is identical to the one indicated in the label placed
on the rear of the UPS
•
Switch on your UPS with the ON/OFF button and check it operates correctly with the
mains (green LED on).
•
Switch the UPS off by pressing the ON/OFF button until the LED shuts down.
•
After switching off the UPS, connect the load power cable to the UPS output using
the outlet located on the right side of the UPS.
•
Switch on your UPS and then the load to check it operates correctly with the mains
(green LED on).
•
Keep the UPS on for 8 hours to recharge battery before using it.
UPS can also be used before battery is completely charged, but in this case back up
time available during black out will be shorter.
Statement of Conformity
Council directives applied: 77/23/EEC 89/336/EEC modified with direct
92/31/EEC, 93/68/EEC
Standard with which conformity is declared:
EN 62040-1-1 EN 50091-2
EN 62040-3
Distributor:
MetaSystem S.p.A.
Address:
Via Majakovskij 10/b, Reggio Emilia, Italy
Type of equipment:
Uninterruptible Power Supply
Model:
Niky 1100/1500 Plus
Year of adding the mark:
2008
The equipment has been tested in its typical installation configuration and
with peripheral devices in conformity with the EMC Directive. As tecnichal
files available in MetaSystem
I the undersigned do declare that the above defined appliance meets the
protection requirements of the above stated EMC Directive
Works Manager
Ing. Cesare Lasagni
NOTICE
Never disconnect the 230 V power plug while the UPS is operating since
this would disconnect the earthing protection both from the UPS and from
the loads connected to it.
CAUTION
While wiring the outlet line, make sure the total length of the cable, from the UPS to the
farthest utility, does not exceed 10 metres.
GB
INTRODUCTION
This manual contains information for users of the DAKER NIKY 1100/1500
Plus models.
You are advised to read this handbook carefully before installing your
uninterruptible power supply, meticulously following the instructions given
herein.
The UPS DAKER NIKY is only been made for civil or industrial use; it is not in
conformity with the standards for electro-medical equipment.
CONDITIONS OF USE
•
The UPS DAKER NIKY has been designed to supply data processing equipment. The
load applied must not exceed the one indicated on the rear label of your UPS.
•
The ON/OFF button of your UPS does not electrically isolate the internal parts. To
isolate your UPS unplug it from the mains power socket.
•
Do not open the UPS container since there may be parts inside with dangerously high
voltage even when the mains plug is disconnected; there are no parts inside that the
user can repair.
•
The UPS DAKER NIKY has been designed to work in closed, clean rooms where there
are no inflammable liquids or corrosive substances and where it is not too damp.
•
Do not place near equipments that generate strong electro-magnetic fields and/or
near equipments that are sensible to electro-magnetic fields. (engines, floppy disks,
speakers, adapters, monitors, video, etc...)
•
Do not pour any liquid on the UPS or inside the UPS.
•
Do not place the UPS in humid environment or near liquid, such as water, chemical
solution…
•
Do not expose the UPS to the direct sunlight or any heat sorces
•
Keep the ventilation slits clean to dissipate the heat of the UPS.
•
Use grounded power cable to connect the UPS to the mains supply.
•
Do not plug laser printers into the UPS because of their high start-up current.
•
Do not plug house electric equipments, such as hair dryer,air conditioner, and
refrigerator into the UPS outlets.
SIGNALS AND CONTROLS
LED indicators:
The different colours of the LEDs on the front panel indicate the following
(Fig. 1):
- LED1: Fixed green:
mains present and regular.
Green flashing every 2 sec:
batteries are recharging
- LED2: Fixed yellow:
no mains (running on battery)
- LED3: Fixed red:
overload alarm.
- LED4: Red flashing every 0.5 sec:
Autonomy in reserve.
Acoustic signals:
•
Intermittent sound every 2 sec:
running on battery
•
Intermittent sound every 0.5 sec:
overload or autonomy in reserve
•
Continuous sound:
failure or generic alarm
OVERLOAD AND SELF-SHUTDOWN
Your UPS is equipped with a system to measure the power delivered at the
outlet; when this exceeds the set thresholds, the protection and relative
signals are activated; shutdown is automatic with a delay in relation to the
size of the overload.
Under the line mode the green led will be light. If the overload is 100% ±
10%; UPS will shutdown after 5 minutes and go to fault mode. If the
overload is 110% ± 10%; UPS will shutdown immediately and go to fault
mode.
Under the battery mode the yellow led will be flashed. If the overload is
100% ± 10%; UPS will be shutdown after 5 second and go to fault mode.
If the overload is 110% ± 10%; UPS will shutdown immediately and go to
fault mode.
FEATURES
•
SELF TEST:
Automatic self text is executed each time the UPS is switched on, to
provide a reliable operation.
•
BATTERY PROTECTION:
Automatic battery test and deep discharge protection.
•
DC START CAPABILITY:
The UPS can be switched on in DC mode (battery operation) rete provided
the load does not exceed 80% of the UPS’ rated power.
•
UPS POWER SUPPLIED OUTLETS:
This is a line interactive UPS equipped with AVR, that allows to feed the
load with a stabilized output voltage even when mains floats.
ELECTRICAL PROTECTION:
Automatic swith off upon short circuit.
CPU MICROPROCESSOR CONTROL
GREEN FUNCTION:
If battery is discharging under no load, UPS will shut down automatically
to save battery life.
FULL TIME SURGE PROTECTION OUTLET
Connect the appliances not needing for back up protection (printers, fax
etc.) to the surge protected outlet located near the back of the unit.
EMI/RFI FILTERING:
Bad quality of mains supply can damage electronic appliances because
of electromagnetic radio frequency interferences. The UPS is provided
with a dedicated filter to eliminat these disturbances.
Reggio Emilia, 12/11/08