background image

DGM01

 – SERVER GATEWAY – FW 3.0

Gateway ETHERNET-MODBUS-DMX512A-DALI

Function manual 

 

 

Made in Italy

Rev. 2016-09-19

pag. 20/22

                       
              

BUS 1  (or BUS 1&2)

 -  

MODBUS RTU MASTER

                            

              DGM01 provides two buses (BUS1 and BUS2) that can be configured
              as  

MODBUS RTU MASTER

 on RS-485 standard.

               Configuration

               Baud rate values can be selected from the following:
                
               - 9600
               - 38400
               - 115200
               - 125000
               - 250000
                     
               Format: 8 bit
               Parity: even, odd, none
               Stop bits: 1 or 2

                The information are transmitted to 80 slaves  (ID 1..80).
                A group of 6 channels  is sent  to each slave:

               - ID1: channels from 1 to 6 are transmitted to registers from 0 to 5
               - ID2: channels from 7 to 12 are transmitted to registers from 0 to 5
               …
               

                                                                                                      - ID80: channels from 475 to 480 are transmitted to registers
                                                                                                                  from 0 to 5

                                                                                                      

The BUS can be disabled by the flag “MUTE”.

                                                                                                      

BUS 1  (oppure BUS 1&2) -  MODBUS RTU SLAVE

  

                   

DGM01 provides two buses (BUS1 and BUS2) that can be configured

                   as  

MODBUS RTU SLAVE

 on RS-485 standard.

                   Configuration

                                                                                                       Baud rate values can be selected from the following:

                    - 9600
                    - 19200
                    - 38400

                                                                                                        - 115200
                                                                                                        - 250000
                                                                                                        - 500000

                  
                    Format: 8 bit
                    Parity: even, odd, none
                    Stop bits: 1 or 2
 
                   The information are received from Modbus.
                    It is possible to read and write 512 registers with value
                    from 0 to 255.
                    ID can be configured by web server interface.

                                                                                                        

The BUS can be disabled by the flag “MUTE”.

Server Gateway

 

CONTROLLERS

DALCNET S.r.l.

Registered office: via Meucci, 35 - 36040 Brendola (VI) - Italy 

Headquarters: via Meucci, 35 - 36040 Brendola (VI) - Italy 

Tel. + 39 0444 1836680/1867452 Fax. + 39 0444 1867453 

VAT: IT-04023100235 

info@dalcnet.com www.dalcnet.com

Summary of Contents for DGM01

Page 1: ...put Current voltage min typ max 12Vdc 110mA 1 2W 320mA 3 84W 500mA 24Vdc 60mA 1 44W 160mA 3 84W 48Vdc 40mA 1 92W 80mA 3 84W ethernet and all bus at full load Storage temperature min 40 max 60 C Ambient temperature min 10 max 40 C Protection Grade ALUMINIUM BOX IP20 PLASTIC BOX IP10 Weigth ALUMINIUM BOX 230g PLASTIC BOX 125g Mechanical dimensions ALUMINIUM BOX 105x70x47 PLASTIC BOX 72x92x62 mm DIN ...

Page 2: ...ep separate the 230V circuits LV and not SELV circuits from safety extra low voltage SELV and all connections for this product It s absolutely forbidden to connect for any reason directly or indirectly the 230V mains voltage to the bus or to other parts of the circuit Power Supply For power supply use only SELV power supplies with limited current and short circuit protection and of appropriately s...

Page 3: ...s factory default DEFAULT IP ADDRESS 192 168 1 4 LEDs LED FUNCTION ON BLINK Fast blink OFF LED1 top Ethernet OK No communication Error LED2 BUS1 DMX RTU OK No communication Error LED3 BUS2 DMX RTU OK No communication Error LED4 bottom BUS DALI OK No communication no power or short circuit Server Gateway CONTROLLERS DALCNET S r l Registered office via Meucci 35 36040 Brendola VI Italy Headquarters ...

Page 4: ...n The device starups turned off in the event of blackout N O push button connected to 0V 3 Preset Function The installer stores the preset status N O push button connected to 5V during installation next to 0V The device starts from the preset in the event of blackout E g connecting local inputs Server Gateway CONTROLLERS SERVER GATEWAY DGM01 1248 DC In Range DALI supply 12 48 V 40 60 C 125mA ETH B...

Page 5: ...at vary more rapidly On the Modbus RTU the first 480 channels of the buffer are transmitted to 80 modbus devices id 1 80 of 6 registers each This default configuration allows to manage a total of 512 levels of light intensity with any control system provided of Ethernet connection and to control different devices without need to know in detail the functioning of the related protocols DMX512A RDM D...

Page 6: ...T DGM01 implements Art Net 3 protocol and can be used as Art Net DMX and Art Net DALI gateway from main softwares and lighting desk UPD 6454 port is used Configuration Implemented packets OpCode Note ArtDmx Sub Net and Universe are routed to the DGM universe ArtPoll Server Gateway CONTROLLERS DALCNET S r l Registered office via Meucci 35 36040 Brendola VI Italy Headquarters via Meucci 35 36040 Bre...

Page 7: ...evice will continue the transmission of last values received For example setting up send 1 byte 2 byte 3 byte 512 byte the first lamp to max level and the others off 255 0 0 0 the second lamp to max level and the others off 0 255 0 0 the second lamp to 50 level and the others off 0 128 0 0 Configuration It is possible to set up a UPD receiving port and a UPD transmission port or make a broadcast t...

Page 8: ...ss from 0 to 511 and value from 0 to 255 TCP 502 port is used the ID slave is not considered Configuration Implemented packets Function Code Function Name 03 Read holding registers 06 Write single register 16 Write multiple registers Tested softwares Brand Name Version Witte Software Modbus Poll 6 4 2 Server Gateway CONTROLLERS DALCNET S r l Registered office via Meucci 35 36040 Brendola VI Italy ...

Page 9: ...number of slots to transmit For example to set send the first lamp to max level and the others off data addr 0000 size 0200 FF000000 00 data the second lamp to max level and the others off data addr 0000 size 0200 00FF0000 00 data the second lamp to 50 level and the others off data addr 0000 size 0200 00800000 00 data the first lamp to max level and the others untouched data addr 0000 size 0001 FF...

Page 10: ...ponding channel Maximum 64 values i e channels can be sent in a single packet so to starting a fade on all 512 channels is required to send at least 8 packets For example to set send the first lamp to max level and the third off with 5 seconds fade time fade time 0032 addr 0000 size 0003 FFXX00 fade To stop the fading of the third lamp at the actual value fade time 0000 addr 0002 size 0001 00 fade...

Page 11: ...0000 6 7 2bytes little endian 512 512 number of slots to write 512 8 9 10 11 4bytes little endian 0 0 first slot to write 0 12 13 14 15 4bytes little endian 0x00000000 0x00000000 0x00000000 0x00000000 16 N bytes do t transmit N 0 512 slot values N 512 transmit N slot values N number of slot to write 512 slot values N 512 The request is sent with the following syntax POST dmem bin HTTP 1 1 r n Host...

Page 12: ... to URL dmx xml through POST method and is enclosed by the tags data data See the section TCP Telnet for the tag data data description The request is sent with the following syntax POST dmx xml HTTP 1 1 r n Host 192 168 1 4 r n r n data addr 0000 size 0200 010203040506070809 data The answer is like this HTTP 1 1 200 OK r n Content Type text plain r n r n data 010203040506070809 data Server Gateway...

Page 13: ...layed All the other channels can be scrolled to be visualized NOTE It is necessary to use an HTML 5 CSS 3 JS XHR CORS JSON ArrayBuffer compliant browser to correctly access to the available services and applications Compatibility with Mozilla Firefox 45 Apple Safari 9 Google Chrome 49 Server Gateway CONTROLLERS DALCNET S r l Registered office via Meucci 35 36040 Brendola VI Italy Headquarters via ...

Page 14: ...nnels Save actual channels level as power on levels value Load Power up Channels Reload Power on channels value saved When a Power cycle is done the device will restart with Power on values previously saved BUS Manager Control and Management of devices connected to BUS network provided for DALI BUS Device Config Configuration Menu of the DGM01 In this section is possible to configure IP address ne...

Page 15: ... function is selected on the drop down menu the Gateway works on its standard operating mode On this operating mode the 64 devices i e a DALI universe that can be managed are displayed in a grid It is possible to display the state of the connected devices directly on the grid every grid box i e every single device can be shown with the following colours GREY the device is not present or does not r...

Page 16: ...magnifying glass The waiting time could be a few minutes tempo di attesa può essere di qualche minuto depending on the type and number of connected devices ERASE SYSTEM Drag ALL box into Remove Address box and release it The addresses of all connected devices will be deleted ADDRESS CHANGE Drag the box from the address that has to be changed and release it on the one chosen The new address becomes...

Page 17: ...ed and sent to the devices on the network are System Failure Level Power On Level Fade Time Note during the execution of commands the interface s display screen becomes translucent SEND PARAMETERS Set up the desired value on each parameter and then press Send Values to transmit the parameters to the connected devices RESET PARAMETERS Press Factory Default to restore factory default parameters valu...

Page 18: ... can be disabled To activate and store desired settings it is necessary to click on Save and Reboot button and wait for DGM01 restart To exit the Device Config page it is necessary to click on Dalcnet logo on the top left side of the interface s display Ethernet TCP IP Settings DGM01 Server Gateway uses Ethernet port with IPv4 protocol Default IP address is 192 168 1 4 NOTE the subnet must be the ...

Page 19: ...time Zero value disables the periodic transmission Ethernet TCP Modbus In this section the port used 502 from MODBUS TCP IP server can be verified Moreover it is possible to configure the sending timing of the response strings from the Telnet server which is able to receive and or transmit a DMX512A RDM universe from to other devices by TCP protocol The connection is established on TCP port 23 Tel...

Page 20: ...annels from 475 to 480 are transmitted to registers from 0 to 5 The BUS can be disabled by the flag MUTE BUS 1 oppure BUS 1 2 MODBUS RTU SLAVE DGM01 provides two buses BUS1 and BUS2 that can be configured as MODBUS RTU SLAVE on RS 485 standard Configuration Baud rate values can be selected from the following 9600 19200 38400 115200 250000 500000 Format 8 bit Parity even odd none Stop bits 1 or 2 T...

Page 21: ...The BUS can be disabled by the flag MUTE BUS 2 oppure BUS 1 2 DMX512 RESPONDER DGM01 provides two buses BUS1 and BUS2 that can be configured as DMX512 RDM RESPONDER SLAVE Simply select the SLAVE option from the drop down menu in order to be able to receive the entire DMX universe A 512 channels universe can be received on both buses BUS1 and BUS2 Configuration No configuration required The BUS can...

Page 22: ... state by the sensor DALI sensors have to be configured as slaves it is possible to specify the quantity of sensors on the network and the research starting address to identify them on the net The BUS can be disabled by the flag MUTE BUS 3 DALI CONTROL GEAR DGM01 provides a bus BUS3 that can be configured as DALI CONTROL GEAR SLAVE Simply select SLAVE option from the drop down menu The device has ...

Reviews: