Dale Power Solutions Ltd
User Manual
24
…………………………………………………………………………………………………………
Front panel controls and indicators
The front panel controls and indicators are shown in
Error! Reference source not found.
. Using the
buttons, LEDs and the menu structure displayed on the LCD panel you can:
■ Check the status of the UPS
■ Check and make changes to the settings
Note:
Your UPS is setup to your requirements by the distributor prior to delivery. There is normally
no reason to change any of the settings.
Figure 9 Front panel controls and indicators
The LCD panel is hinged along its top edge and can be pulled out at the bottom to create different
viewing angles if required. It is also possible to connect a second LCD for remote monitoring and control.
Contact your distributor for details.
Caution:
To ensure no one accidentally catches a tilted panel it is advisable to return it to its
vertical position when not in use.
The following table describes the operation of the LED indicators:
LED
Colour
Description
Output
Green
On when the load is being supplied
Inverter
Green
On when the UPS is supplying power. Flashes when the inverter is overloaded or it is faulty
Battery
Green
On when power is supplied from the battery. Flashes if the battery is low, disconnected, reversed
polarity, not charging or if the voltage is abnormally high
Mains
Green
On when mains is present and within limits. Flashes if the mains is outside its normal range
Bypass
Green
On when power is supplied via the bypass. Flashes when the bypass is not available, out of