15
3.4 Technical features
Tab.3.4.1
details all technical features of the ”CSA GM” mod. generators. Tab.
3.5
shows
the overall dimensions of all models.
For any other information, please contact the technical department of D’ALESSANDRO
TERMOMECCANICA s.r.l.
BOILERS MODELS
CSA30
GM
CSA45
GM
CSA60
GM
CSA80
GM
CSA100
GM
nominal power
(kW)
30
45
60
80
100
power to firebox
(kW)
34.9
52
71
94
115
max working pressure
(bar)
3
hydraulic test pressure
(bar)
4.5
max working temperature
(°C)
90
mains voltage
(V)
230
electric utilities absorption (excluding optionals)
(kWh)
1.13
regime fuel consumption
(¹)
(Kg/h)
7.1
10.6
14.4
19.2
23.4
hopper volume
(dcm³)
480
water side load loss (10K)
(mbar)
32
58
72
87
109
water side load loss (20K)
(mbar)
13
16
31
49
61.3
pump activation minimum temperature
(°C)
40
boiler water content
(l.)
130
155
205
255
305
fumes average temperature (clean boiler)
(°C)
170 (
20%)
chimney draught depression
(Pa)
-20 (
30%)
fumes chimney diameter
(mm)
200
combustion chamber volume
(dcm³)
95
115
135
175
215
L x H combustion chamber opening dimensions
(mm)
490x395
boiler empty mass (tolerance
±
5%)
(Kg)
400
500
650
750
850
thermal drain valve capacity (Δt=80°C at 1.5 bar)
(l./h)
1882
(¹)
the l.h.v. (lower heat value) of reference of the fuel is equal to 17.6 MJ/Kg (4.9 kWh/kg), as from prospectus 8 of Standard
EN303-5 for test type "C" fuel
tab. 3.4.1