System alarms
The alarm priority can not be altered on system alarms
Medium
Clock has not been set
Time has not been set
Medium
System Critical exception
A unrecoverable critical system failure has occurred – exchange the controller
Medium
System alarm exception
A minor system failure has occurred – power off controller
Medium
Alarm destination disabled
When this alarm is activated the alarm transmission to the alarm receiver has been deactivated.
When the alarm is cleared the alarm transmission to the alarm receiver has been activated.
Medium
Alarm route failure
Alarms can not be transmitted to alarm receiver – check communication
High
Alarm router full
The internal alarm buffer has an overrun – this might occur if the controller can not send the alarms
to the alarm receiver. Check communication between controller and AKA gateway.
Medium
Device is restarting
The controller is restarting after flash updating of the software
Medium
IO module error
There is a communication fault between the controller module and the extension modules – the
fault must be corrected as soon as possible
Low
MAN DI……….
The output in question has been put in manual control mode via the AK-ST 500 service tool soft-
ware
Low
MAN DO………
The output in question has been put in manual control mode via the AK-ST 500 service tool soft-
ware