Installing the Optional Strain Relief
As an alternative to installing the sub D9 connector, an
optional strain relief is included in the kit. It can be used to
support the PROFIBUS module cabling and to provide non-
IP54 shield termination. If the strain relief is used, do not
install the sub D9 connector. Use the following steps to install
the strain relief.
1.
Remove the front cover from the drive.
2.
Remove the local control panel (LCP). See
Illustration 1.1
.
3.
Remove the LCP cradle by pulling the cradle
outward.
4.
Unfasten 2 M5 nuts (8 mm) from the underside of
the left cover plate, and remove the plate from the
drive enclosure. See
Illustration 1.7
.
5.
Position the strain relief over the screw hole in the
upper right corner above the PROFIBUS module. See
Illustration 1.8
.
6.
Fasten 1 M4 thread-cutting screw (T10), securing the
strain relief in place.
1
Bottom of left cover plate
2
M5 nut
3
Top of drive enclosure
Illustration 1.7 Bottom View of Left Cover Plate from Inside
Enclosure
1
M4 thread-cutting screw
2
Strain relief
Illustration 1.8 Strain Relief Installation
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on
order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss
and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MI38Q302*
MI38Q302
175R5964
10/2017