background image

Description

The mains shield kit fits the following drives in E1h/E2h
enclosures:

VLT

®

 HVAC Drive FC 102

VLT

®

 Refrigeration Drive FC 103

VLT

®

 AQUA Drive FC 202

VLT

®

 AutomationDrive FC 302

The kit adds a Lexan shield over the mains terminals and
busbars to provide protection against accidental touch of the
power terminals, according to BGV A2, VBG 4.

Kit Part Numbers

Use these instructions with the following kits.

Kit number

Kit description

176F6619

Mains shield assembly for E1h drive

176F6620

Mains shield assembly for E2h drive

Table 1.1 Part Numbers for Kits

Items Supplied

The mains shield kit contains the following items.

Item

Quantity

Upper shield

1

Lower shield

1

Brackets

14

M5x12 screw/washer assembly

28

Table 1.2 Items Supplied in Mains Shield Kit

Safety Information

WARNING

ELECTRICAL SHOCK HAZARD

VLT

®

 series drives contain dangerous voltages when

connected to mains voltage. Improper installation, and
installing or servicing with power connected, can cause
death, serious injury, or equipment failure.

To avoid death, serious injury, or equipment failure:

Only use qualified electricians for the installation.

Disconnect the drive from all power sources before
installation or service.

Treat the drive as live whenever the mains voltage
is connected.

Follow the guidelines in these instructions and local
electrical safety codes.

WARNING

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High voltage
can be present even when the warning LED indicator lights
are off. Failure to wait 40 minutes after power has been
removed before performing service or repair work can result
in death or serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and DC-
link connections to other drives.

Disconnect or lock PM motor.

Wait 40 minutes for capacitors to discharge fully.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Installation Instructions

Mains Shield Kit for E1h/E2h Drives
VLT

®

 Series FC 102, FC 103, FC 202, and FC 302

Danfoss A/S © 08/2017 All rights reserved.

MI35I102