Service Guide
|
Controller replacement AK-CC 750 on AK-SM 800
© Danfoss | ADAP-KOOL® | 2018.08
4 | AX278947943210en-000101
7. Now navigate to Control->Refrigeration->Circuits->Setup. In
the drop-down on the left, locate the case controller being
replaced. If prompted at any point to ‘retrieve configuration’, be
sure to select no.
8. Choose ‘Select Application’ from the drop-down on the right,
and ensure Main Switch is set to ‘OFF’ and Configuration Lock
set to ‘Unlocked’. If not, scroll to setting so that it is highlighted,
and press OK key on keypad to toggle to correct option.
9. Now navigate to Download tab, highlight and press OK key
on ‘press to deselect all’. Next, highlight the case controller to
download to, and press OK. This should place a check mark in
the box next to the controller address.