28
User
Guide RS8GR602 © Danfoss 2016-10
AK-CT
450A
Fan pause while night blind rolls down
Here you can set the fan pause time, so the night blind can roll down unhindered
to the correct position.
P65
BlindFanStop
Max. on time for light after manual DI activation
Delay time before light goes off again after light has been turn on manual due to
product stocking.
P66
Light On Time
Case shutdown
Service
Service
Temperature measured with S5 sensor
u09
S5 temp.
Status on DI1 input. on/1=closed
u10
DI1 status
Read the duration of the ongoing defrost or the duration of the last completed
defrost.
u11
Defrost time
Temperature measured with S3 sensor
u12
S3 air temp
Status at the day-/night operation (night operation: on/off)
u13
Night Cond.
Temperature measured with S4 sensor
u16
S4 air temp
Thermostat temperature
u17
Ther. air
Read the ongoing cutin time for the thermostat or the duration of the last
completed cutin
u18
Ther runtime
Read the valve’s actual opening degree
u23
Valve OD %
Read the temperature at the S6 sensor
u36
S6 temp
Status on DI2 input. on/1=closed
u37
DI2 status
Air temperature. Weighted S3 + S4
u56
Display air
Measured temperature for alarm thermostat
u57
Alarm air
* Status on relay for cooling
u58
Comp1/LLSV
Status on relay for fan
u59
Fan relay
* Status on relay for defrost
u60
Def. relay
Status on relay for railheat
u61
Railh. relay
* Status on relay for alarm
u62
Alarm relay
Status on relay for light
u63
Light relay
* Status on relay for hot gas valve
u64
SuctionValve
* Status on relay for compressor 2
u67
Comp2 relay
* Temperature measured with S5B sensor
u75
S5 temp. B
* Temperature measured with S3B sensor
u76
S3 air temp B
* Temperature measured with S6B sensor
u79
S6 temp. B
* Status on relay for hot gas
u80
Hotgas valve
* Status on relay for heating element in drip tray
u81
Drip tray
* Status on relay for night blinds
u82
Blinds relay
* Status on relay for defrost 2
u83
Def. relay 2
* Readout of the actual rail heat effect in %
u85
Rail DutyC %
Readout of which thermostat used for regulation: 1= Thermostat 1,
2= Thermostat 2
u86
Ther. band
Status on input DI3 (closed / open)
u87
DI3 status
Readout of the actual cutin value for the thermostat
u90
Cutin temp.
Readout of the actual cut out value for the thermostat
u91
Cutout temp.
* Measured temperature for alarm thermostat for B section
U34
Alarm air B
* Air temperature. Weighted S3 + S4 temp. for B section
U35
Display air B
* Status of relay for light 2
U36
Extra light
* Status of relay for ECO fan
U37
Fan Eco
* Status of relay for defrost 3
U38
Def. relay 3
Status of DI4 input. On=closed
U39
DI4 status
Status of DI5 input. On=closed
U40
DI5 status
Status of DI6 input. On=closed
U41
DI6 status
Status of high-voltage input DI7, 230 V = 1 = closed
U42
DI7 status
Status of high voltage input DI8, 230 V = 1 = closed
U43
DI8 status
0-10 V output indicates EVR valve’s degree of opening
U44
AO1 voltage