AK-CT
450A
User
Guide RS8GR602 © Danfoss 2016-10
37
Input signal on DI5. Contact switch. See DI3 above
P56
1
1
1
1
1
1
1
1
0
19
0
Input signal on DI6. Contact switch. See DI3 above
P57
1
1
1
1
1
1
1
1
0
19
0
Input signal on DI7. High voltage signal. See DI3 above
P58
1
1
1
1
1
1
1
1
0
19
0
Input signal on DI8. High voltage signal. See DI3 above
P59
1
1
1
1
1
1
1
1
0
19
0
Max. opening time of night blind following manual override
with DI activation.
P60
1
1
1
1
1
0 min.
60 min.
5
Erase all current controller settings on ID module.
P61
1
1
1
1
1
1
1
1
0 / off
1 / on
0 / off
Configuration of night blind relay. On= night blind used
P64
1
1
1
1
1
0 / off
1 / on
1 / on
Stop time for fan while night blind rolls down
P65
1
1
1
1
1
0 sec
300 sec
60
Max. on time for light and night blind following manual
DI activation
P66
1
1
1
1
1
1
1
1
0 min.
60 min.
30
Real time clock
t-
Six start times for defrost.
Setting of hours.
0=OFF
t01 -
t06
1
1
1
1
1
1
1
1
0 hrs
23 hrs
0
Six start times for defrost.
Setting of minutes.
0=OFF
t11 -
t16
1
1
1
1
1
1
1
1
0 min.
59 min.
0
Clock - Setting of hours
t07
1
1
1
1
1
1
1
1
0 hrs
23 hrs
0
Clock - Setting of minute
t08
1
1
1
1
1
1
1
1
0 min.
59 min.
0
Clock - Setting of date
t45
1
1
1
1
1
1
1
1
1 day
31 day
1
Clock - Setting of month
t46
1
1
1
1
1
1
1
1
1 mon.
12 mon.
1
Clock - Setting of year
t47
1
1
1
1
1
1
1
1
0 year
99 year
0
Service
u-
Temperature measured with S5 sensor
u09
1
1
1
1
1
1
1
1
Status on DI1 input. on/1=closed
u10
1
1
1
1
1
1
1
1
Actual defrost time (minutes)
u11
1
1
1
1
1
1
1
1
Temperature measured with S3 sensor
u12
1
1
1
1
1
1
1
1
Status on night operation (on or off) 1=on
u13
1
1
1
1
1
1
1
1
Temperature measured with S4 sensor
u16
1
1
1
1
1
1
1
1
Thermostat temperature
u17
1
1
1
1
1
1
1
1
Run time of thermostat (cooling time) in minutes
u18
1
1
1
1
1
1
1
1
Opening degree of EVR valve
**
u23
1
1
1
1
1
1
1
1
Temperature measured with S6 sensor
(product temperature)
u36
1
1
1
1
1
1
1
1
Status on DI2 input. on/1=closed
u37
1
1
1
1
1
1
1
1
Air temperature . Weighted S3 and S4
u56
1
1
1
1
1
1
1
1
Measured temperature for alarm thermostat
u57
1
1
1
1
1
1
1
1
Status on relay for cooling
**
u58
1
1
1
1
1
1
1
Status on relay for fan
**
u59
1
1
1
1
1
1
1
1
Status on relay for defrost
**
u60
1
1
1
1
1
1
1
Status on relay for rail heat
**
u61
1
1
1
1
1
1
1
1
Status on relay for alarm
**
u62
1
1
1
1
1
1
1
1
Status on relay for light
**
u63
1
1
1
1
1
1
1
1
Status on relay for hot gas valve
**
u64
1
Status on relay for compressor 2
**
u67
1
Temperature measured with S5B sensor
u75
1
1
1
1
1
1
1
1
Temperature measured with S3B sensor
u76
1
1
1
1
Temperature measured with S6B sensor
u79
1
1
1
1
Status on relay for hot gas valve / drain valve
**
u80
1
Status on relay for heating element in drip tray
**
u81
1
Status on relay for night blinds
**
u82
1
1
1
1
1
Status on relay for defrost 2
**
u83
1
1
1
Readout of the actual rail heat effect
u85
1
1
1
1
1
1
1
1
1: Thermostat 1 operating, 2: Thermostat 2 operating
u86
1
1
1
1
1
1
1
1
Status on DI3 input. on/1=closed
u87
1
1
1
1
1
1
1
1
Readout of thermostats actual cut in value
u90
1
1
1
1
1
1
1
1
Readout of thermostats actual cut out value
u91
1
1
1
1
1
1
1
1
Measured temperature for alarm thermostat in section B
U34
1
1
1
1
Air temperature in section B
U35
1
1
1
1
Status of relay for light 2
**
U36
1
1
1
1
1
1
Continued
Code 1 2 3 4 5 6 7 8
Min.
Max.
Fac.
Actual