background image

load

motor

 [%]: Percentage value of the torque-

producing component or torque-producing
current in the motor in the range 0–1. The value
is typically from the design of the application.

The IEC 61800-9-2 standard for 

Ecodesign of Power Drive

Systems

 allows the use of reference values. Determine the

motor cosine phi value by the motor nominal power rating
as kVA and with linear interpolation from the reference
values in 

Table 9.1

.

Nominal power [kVA]

Current [%]

Cosine phi

0.278

100

0.73

1.29

100

0.79

7.94

100

0.85

56.9

100

0.86

245

100

0.87

Table 9.1 Motor Reference Values from IEC 61800-9-2

9.1.6.1 Calculation Example

The frequency converter used in the example is a VLT

®

AutomationDrive FC 302, T5, 22 kW with Class A1/B RFI
filter and enclosure protection rating IP20.

Frequency converter values

I

out,VLT

=44 A.

Cos phi=0.85.

f

motor

 [%]=25 Hz, resulting in 50%.

load

motor

 [%]=33 A, resulting in 75% (33 A/44 A x

100).

In the example, VLT

®

 Advanced Harmonic Filter AHF 010

with order number 130B1111 is selected as filter. See

Table 5.3

 for further specifications of the filter.

AHF values

40 A nominal current.

AHF 010, THDi = 10%.

IP20.

Calculating the frequency converter input current

I

In,VLT

=I

out,VLT

 x cos(phi) x f

motor

 [%] x load

motor

 [%] x 1.02

I

In,VLT

=44 x 0.85 x 0.50 x 0.75 x 1.02=14.3 A

Calculating the AHF input current

I

In,AHF

=I

In,VLT

=14.3 A

Calculating the power loss

Matching values from the tables in 

chapter 7.3 Power

Loss and Acoustic Noise Level

86 W power loss at 10 A current loading.

142 W power loss at 20 A current loading.

Determining the power loss, Loss

OPT

, in AHF point of

operation load

OPT

 using 2-dimensional interpolation

Loss

2

=142 W.

Loss

1

=86 W.

Load

2

=20 A.

Load

1

=10 A.

Load

OPT

 = Load

AHF

 = Load of AHF in point of

operation = 14.3 A.

Loss

OPT

 = Loss

AHF

 = Loss in AHF in point of

operation.

Loss [W]

Loss

2

142 W

Loss

OPT

Loss

1

86 W

Load

1

10 A

Load

OPT

14.3 A

Load

2

20 A

Load [A]

130BE895.10

Illustration 9.5 Determining Power Loss with 2-dimensional
Interpolation

Loss

OPT

 = Loss

1

 + (Loss

2

 - Loss

1

) x ((Load

OPT

 – Load

1

) /

(Load

2

 – Load

1

))

Loss

OPT

 = Loss

AHF

 = 86 + (142 - 86) x ((14.3 - 10) / (20 - 10))

= 110 W

For system calculations and energy efficiency report, use
the MyDrive ecoSmart tool.

The power loss of the frequency converter provided by
MyDrive ecoSmart:

Power loss @ 50% motor frequency and 50%
motor current = 249 W.

Power loss @ 50% motor frequency and 100%
motor current = 490 W.

The power loss of the frequency converter at 50% motor
frequency and 75% torque-producing current are found by
2-dimensional interpolation as 370 W.
Loss

VLT

 = 370 W.

Alternatively, identify the power loss of the frequency
converter by entering the point of operation in MyDrive
ecoSmart as a user-defined operating point.

To determine the power loss of the CDM, sum up the
power losses in the operating point of the AHF and the
frequency converter:
Loss

CDM

 = Loss

AHF

 + Loss

VLT

 = 110 W + 370 W = 480 W

Appendix

Design Guide

MG80C602

Danfoss A/S © 05/2019 All rights reserved.

119

9

9

Summary of Contents for AHF 010

Page 1: ...NEERING TOMORROW Design Guide VLT Advanced Harmonic Filter AHF 005 AHF 010 VLT HVAC Drive FC 102 VLT Refrigeration Drive FC 103 VLT AQUA Drive FC 202 VLT AutomationDrive FC 301 302 vlt drives danfoss...

Page 2: ......

Page 3: ...rmonics and Mitigation 9 2 1 1 Linear Loads 9 2 1 2 Non linear Loads 9 2 1 3 The Effect of Harmonics in a Power Distribution System 11 2 2 Harmonic Mitigation Standards and Requirements 12 2 2 1 Appli...

Page 4: ...ories 34 5 3 1 IP21 NEMA 1 Upgrade Kit 34 5 3 1 1 IP21 NEMA 1 Upgrade Kit without Built in Capacitor Disconnect Circuitry 35 5 3 1 2 IP21 NEMA 1 Upgrade Kit with Built in Capacitor Disconnect Circuitr...

Page 5: ...uction to Energy Efficiency 116 9 1 2 IE and IES Classes 117 9 1 3 Power Loss Data and Efficiency Data 117 9 1 4 Losses and Efficiency of a Motor 118 9 1 5 Losses and Efficiency of a Power Drive Syste...

Page 6: ...inery Directive 2006 42 EC Observe EN 60204 The VLT Advanced Harmonic Filter AHF 005 AHF 010 is intended for use with VLT HVAC Drive FC 102 VLT Refrigeration Drive FC 103 VLT AQUA Drive FC 202 VLT Aut...

Page 7: ...s a simple way of showing whether a product complies with the relevant EU directives and standards The CE label says nothing about the specifi cations or quality of the product 1 5 2 CE Mark Illustrat...

Page 8: ...pact of energy related products includes energy consumption throughout the entire product life cycle The RCM Mark label indicates compliance with the applicable technical standards for electromagnetic...

Page 9: ...afe separation from the supply line to VDE 0100 include all control wiring in further protective measures for example double insulated or shielded grounded and insulated CAUTION HOT SURFACE When in us...

Page 10: ...transport and handling Components are not allowed to be bent Do not alter the distance in between isolation Avoid touching electronic components and contacts Introduction VLT Advanced Harmonic Filter...

Page 11: ...nts Real power P Reactive power Q Apparent power S The apparent power is S U I where S kVA P kW and Q kVAR In the case of a perfectly sinusoidal waveform P Q and S can be expressed as vectors that for...

Page 12: ...6 7 0 0 0 1 1 2 3 4 5 6 7 0 0 0 130BB539 10 Illustration 2 3 Sinusoidal Waveforms Introduction to Harmonics a VLT Advanced Harmonic Filter AHF 005 AHF 010 10 Danfoss A S 05 2019 All rights reserved M...

Page 13: ...is a weighted harmonic distortion that contains only the harmonics between the 14th and the 40th as shown in the following definition PWHD h 14 40 Ih I1 2 100 2 1 3 The Effect of Harmonics in a Power...

Page 14: ...harmonics Example Two 110 kW motors are connected to a 250 kVA transformer One motor is connected direct online and the other is supplied through a frequency converter If the direct online motor shou...

Page 15: ...n planning installations IEEE 519 IEEE recommended practices and requirements for harmonic control in electrical power systems Control of the voltage distortion at the PCC to a TDD of 5 and limitation...

Page 16: ...61000 3 2 The situation is similar in Australia and New Zealand with the prefixes AS NZS Categories of harmonic solutions Passive Active Passive solutions consist of capacitors inductors or a combina...

Page 17: ...type code AHF DA 34 400 50 20 A The values in Table 3 1 are measured for different load currents using a harmonic analyzer Iline RMS Basic current at 50 Hz I1 RMS THDi Total harmonic current Ih RMS A...

Page 18: ...ation 3 5 AHF 005 130BB583 10 0 0 20 40 60 80 100 Load 5 10 15 20 25 0 unbalance 1 unbalance 2 unbalance 3 unbalance THiD average Illustration 3 6 AHF 010 3 1 1 Power Factor In no load conditions the...

Page 19: ...cy converter Therefore always use a capacitor disconnect in generator applications and consider the design carefully For more information about capacitive currents refer to chapter 4 2 1 1 Terminals f...

Page 20: ...ting the load When installing the filter use the lifting eyes on both sides to lift the filter Lift the filters using the dedicated lifting eyes For enclosure X3 V3 to X8 V3 extra lifting eyes are pla...

Page 21: ...ation 4 1 Lifting Method Internal Fan Filters e30bh439 10 Illustration 4 2 Recommended Lifting Method External Fan Filters Requirements for Installati Design Guide MG80C602 Danfoss A S 05 2019 All rig...

Page 22: ...ground Use grounding and potential equalization wires with a cross section as wide as possible minimum 10 mm2 8 AWG or thick grounding tapes Use copper or tinned copper shielded wires only as steel sh...

Page 23: ...rder a backplate thickness 2 mm 0 08 in shown in Illustration 4 4 See Table 5 12 for order number For information about the backplate dimensions see chapter 7 4 4 Backplate Dimensions 130BB636 12 Illu...

Page 24: ...7 Internal fan Standard fan mounted inside the filter enclosure External fan Standard fan mounted outside the filter enclosure e30be606 10 Illustration 4 6 Fan Concept Internal Fan e30be608 10 Illustr...

Page 25: ...nverter can be used for controlling the relay of an external contactor See chapter 6 Programming for more information NOTICE The capacitor disconnect feature does not apply to VLT AutomationDrive FC 3...

Page 26: ...ad C in Illustration 4 10 is a few percentages Illustration 4 10 shows the insertion loss in the frequency converter as a function of load NOTICE The voltage boost causes the voltage at the frequency...

Page 27: ...pens Each filter contains 3 thermal switches mounted in series in each inductor group At temperatures above 140 C 284 F the switches open NOTICE It is mandatory to use the integrated temperature switc...

Page 28: ...tained at nominal filter load Using an oversized filter most likely results in reduced THDi performance If connecting several frequency converters to the same filter size the AHF according to the sum...

Page 29: ...ed values when paralleling filters AHF 005 AHF version with a performance level of 5 THDi or better at system level with nominal load AHF 010 AHF version with a performance level of 10 THDi or better...

Page 30: ...V3 IP20 if 200 381 381 130B1260 130B1217 X8 V3 IP20 ef X7 V3 IP20 if 250 463 480 130B1261 130B1228 X8 V3 IP20 ef X8 V3 IP20 ef 315 590 608 2 x 130B1259 2 x 130B1216 See individual filters 355 647 650...

Page 31: ...544 X8 V3 IP20 ef X7 V3 IP20 ef 200 381 381 130B2872 130B2855 X8 V3 IP20 ef X7 V3 IP20 ef 250 463 480 130B2873 130B2856 X8 V3 IP20 ef X8 V3 IP20 ef 315 590 608 2 x 130B2871 2 x 130B2819 See individual...

Page 32: ...3 IP20 if 160 250 291 291 291 130B1766 130B1498 X8 V3 IP20 if X7 V3 IP20 if 200 300 348 355 355 130B1768 130B1499 X8 V3 IP20 ef X7 V3 IP20 ef 380 380 130B31673 130B31653 X8 V3 IP20 ef X7 V3 IP20 ef 25...

Page 33: ...X7 V3 IP20 ef 160 200 189 197 197 130B5258 130B5224 X7 V3 IP20 ef X7 V3 IP20 ef 200 250 234 240 240 130B5259 130B5225 X8 V3 IP20 ef X7 V3 IP20 ef 250 300 286 296 296 130B5260 130B5226 X8 V3 IP20 ef X8...

Page 34: ...ef X7 V3 IP20 ef 160 198 197 197 197 130B5197 130B5292 X7 V3 IP20 ef X7 V3 IP20 ef 200 245 240 240 240 130B5198 130B5293 X8 V3 IP20 ef X7 V3 IP20 ef 250 299 296 296 296 130B5199 130B5294 X8 V3 IP20 e...

Page 35: ...204 171 204 154 183 154 183 77 87 109 128 77 87 109 128 77 87 109 128 77 87 109 128 X6 CI 98 037H3040 32 251 304 251 304 325 381 251 251 304 325 381 231 231 291 355 380 155 197 155 197 240 155 197 155...

Page 36: ...mounted on a filter with external fan However the kit is used for filters with both internal and external fan and does not vary according to fan type e30be591 10 Illustration 5 1 IP21 NEMA 1 Kit Inte...

Page 37: ...2 29 22 29 22 29 19 25 19 25 X2 V3 IP20 if ef IP21 NEMA1 Kit for AHF3 X2 175U3275 34 40 55 34 40 55 34 40 55 34 40 55 31 36 48 31 36 48 15 20 24 15 20 24 15 20 24 15 20 24 X3 V3 IP20 if ef IP21 NEMA1...

Page 38: ...15 20 24 15 20 24 X3 V3 IP20 if ef IP21 NEMA1 Kit for AHF3 X3 and contactor CI 30 175U5905 66 82 66 82 66 82 66 82 60 73 60 73 29 36 29 36 29 36 29 36 X4 V3 IP20 if ef IP21 NEMA1 Kit for AHF3 X4 and...

Page 39: ...ection wire is delivered looped at terminal X6 from the factory Refer to Table 5 11 for selecting the correct terminal for jumper connection 2 Relay on the control card of the frequency converter Illu...

Page 40: ...IP21 To avoid false airflow when mounting the filter on rails order a backplate For more information see chapter 7 4 4 Backplate Dimensions The backplates are valid for filters revision 1 2 and 3 Orde...

Page 41: ...are used for selecting various functions in the frequency converter Table 6 2 shows which functions can be assigned to digital inputs Functions in group 1 have higher priority than functions in group...

Page 42: ...inal 1 Reset Resets frequency converter after a trip alarm Not all alarms can be reset 2 Coast inverse Default digital input 27 Coast stop inverted input NC The frequency converter leaves the motor in...

Page 43: ...point of enable condition to be used for 21 Speed up and 22 Speed down If speed up speed down is used the speed change always follows ramp 2 parameter 3 51 Ramp 2 Ramp Up Time and parameter 3 52 Ramp...

Page 44: ...amp bit 1 0 Ramp 1 0 0 Ramp 2 0 1 Ramp 3 1 0 Ramp 4 1 1 Table 6 5 Preset Ramp Bit 40 Latched Precise Start A latched precise start only requires a pulse of 3 ms on terminals 18 or 19 When using for pa...

Page 45: ...the feature is activated under voltage limits and enable voltage limits is reduced so that the drive can be operated with 230V single phase UPS supply 96 Mains Loss Select to improve kinetic back up...

Page 46: ...function is defined in parameter 17 80 Homing Function 117 Touch Sensor NOTICE This option is available only with software version 48 XX Normally open contact Serves as a reference for touch probe po...

Page 47: ...5 12 Terminal 27 Digital Input Functions are described in parameter group 5 1 Digital Inputs Option Function 0 No operation 1 Reset 2 Coast inverse 3 Coast and reset inv 4 Quick stop inverse 5 DC brak...

Page 48: ...Quick stop inverse 5 DC brake inverse 6 Stop inverse 8 Start 9 Latched start 5 13 Terminal 29 Digital Input Select the function from the available digital input range and the additional options 60 Co...

Page 49: ...option relevant for the VLT Advanced Harmonic Filter AHF 005 AHF 010 Refer to the frequency converter programming guide for the complete list of options in this parameter Option Function 188 AHF Capa...

Page 50: ...re VLT Advanced Harmonic Filter AHF 005 AHF 010 is used on supply grids with high short circuit ratio Fluctuations can often be recognized by increased acoustic noise and in extreme cases by unintende...

Page 51: ...n 7 1 Power derating altitude above sea level 1000 m 3280 ft without derating 1000 4000 m 3280 13123 ft 5 per 1000 m 3280 ft Table 7 1 General Technical Data 1 The fan control system supports extended...

Page 52: ...ration test Base standard DIN EN 600068 2 6 Test specification 5 13 2 Hz 150 Hz 2 mm 0 08 in peak to peak 0 7 g Packaging ISPM 15 Enclosure protection rating IP20 Optional IP21 NEMA1 upgrade kits Appr...

Page 53: ...ominal current Acoustic noise dB A 0 W 25 W 50 W 75 W 100 W 0 W 25 W 50 W 75 W 100 W 10 130B1229 28 36 66 91 142 70 130B1027 17 22 38 54 86 70 14 130B1231 37 56 85 132 177 70 130B1058 36 50 72 106 137...

Page 54: ...nd Acoustic Noise Level 380 415 V 60 Hz 440 480 V 60 Hz AHF 005 AHF 010 Current rating A Order number P N Power loss at percentage load of nominal current Acoustic noise dB A Order number P N Power lo...

Page 55: ...7 Power Loss and Acoustic Noise Level 600 V 60 Hz 500 690 V 50 Hz AHF 005 AHF 010 Current rating A Order number P N Power loss at percentage load of nominal current Acoustic noise dB A Order number P...

Page 56: ...14 9 245 9 6 58 128 X3 V3 IP20 if 66 130B1241 621 24 5 378 14 9 338 13 3 76 168 X4 V3 IP20 if 82 130B1247 621 24 5 378 14 9 338 13 3 98 216 X4 V3 IP20 ef 96 130B1248 736 29 418 16 5 333 13 1 104 229 X...

Page 57: ...205 452 X8 V3 IP20 ef Table 7 10 AHF 010 380 415 V 50 Hz 380 415 V 60 Hz AHF 005 Current rating A Order number P N Dimensions Weight kg lb Enclosure type Height mm in Width mm in Depth mm in 10 130B28...

Page 58: ...IP20 ef Table 7 12 AHF 010 380 415 V 60 Hz 440 480 V 60 Hz AHF 005 Current rating A Order number P N Dimensions Weight kg lb Enclosure type Height mm in Width mm in Depth mm in 10 130B1752 322 12 7 19...

Page 59: ...7 37 7 468 18 4 451 17 8 172 379 X7 V3 IP20 ef 436 130B1751 957 37 7 468 18 4 515 20 3 205 452 X8 V3 IP20 ef Table 7 14 AHF 010 440 480 V 60 Hz 600 V 60 Hz AHF 005 Current rating A Order number P N Di...

Page 60: ...395 130B5228 957 37 7 468 18 4 515 20 3 260 573 X8 V3 IP20 ef Table 7 16 AHF 010 600 V 60 Hz 500 690 V 50 Hz AHF 005 Current rating A Order number P N Dimensions Weight kg lb Enclosure type Height mm...

Page 61: ...ef 77 130B5287 764 30 1 418 16 5 405 15 9 74 163 X6 V3 IP20 ef 87 130B5288 764 30 1 418 16 5 405 15 9 85 187 X6 V3 IP20 ef 109 130B5289 764 30 1 418 16 5 405 15 9 105 231 X6 V3 IP20 ef 128 130B5290 7...

Page 62: ...14 10 14 X1 0 5 10 20 8 Cable end sleeve 1 6 14 2 10 0 5 4 20 12 Cable end sleeve 0 8 7 1 10 0 5 4 20 12 Cable end sleeve 0 8 7 1 10 M6 4 5 40 10 22 29 22 29 X2 1 5 16 16 6 2 4 21 2 10 0 5 4 20 12 0 8...

Page 63: ...16 6 2 4 21 2 10 0 5 4 20 12 0 8 7 1 10 M6 4 5 40 10 34 40 55 34 40 55 X3 1 5 25 16 4 3 5 31 10 1 5 16 16 6 2 4 21 2 10 M8 10 88 5 10 66 82 66 82 X4 1 5 50 16 1 1 0 4 35 4 10 1 5 25 16 4 3 5 31 10 M8...

Page 64: ...0 5 4 20 12 0 8 7 1 10 M6 4 5 40 10 31 36 48 31 36 48 X3 1 5 25 16 4 3 5 31 10 1 5 16 16 6 2 4 21 2 10 M8 10 88 5 10 60 73 60 73 X4 1 5 50 16 1 1 0 4 35 4 10 1 5 25 16 4 3 5 31 10 M8 10 88 5 10 95 11...

Page 65: ...0 5 4 20 12 Cable end sleeve 0 8 7 1 10 M8 10 88 5 10 29 36 29 36 X4 1 5 50 16 1 1 0 4 35 4 10 1 5 25 16 4 3 5 31 10 M8 10 88 5 10 50 58 50 58 X5 10 70 8 2 0 5 44 3 10 1 5 25 16 4 3 5 31 10 M8 10 88 5...

Page 66: ...le end sleeve 0 8 7 1 10 M8 10 88 5 10 29 36 29 36 X4 1 5 50 16 1 1 0 4 35 4 10 1 5 25 16 4 3 5 31 10 M8 10 88 5 10 50 58 50 58 X5 10 70 8 2 0 5 44 3 10 1 5 25 16 4 3 5 31 10 M8 10 88 5 10 77 87 109 1...

Page 67: ...in 6 5 1 0 mm 0 3 0 04 in 322 0 2 5 mm 12 7 0 10 in 277 8 1 0 mm 10 9 0 04 in e30BB599 11 PE M6 10Nm Illustration 7 2 IP20 X1 V3 Internal Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4 3 X2 2...

Page 68: ...in e30be368 10 PE M6 10Nm Illustration 7 4 IP20 X1 V3 External Fan e30be369 10 A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4 3 X2 2 X2 3 X1 Mains 6mm 1 6Nm A B Temperature 2 5mm 0 8Nm X3 X4 Capa...

Page 69: ...0 1 0 mm 18 1 0 04 in e30bb597 11 PE M6 10Nm Illustration 7 6 IP20 X2 V3 Internal Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4 3 X2 2 X2 3 e30be370 10 X1 Mains 10mm 2 4Nm X2 Drive 10mm 2 4...

Page 70: ...e30bb598 11 PE M6 10Nm Illustration 7 8 IP20 X2 V3 External Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4 3 X2 2 X2 3 e30be370 10 X1 Mains 10mm 2 4Nm X2 Drive 10mm 2 4Nm X3 X4 Capacitor disc...

Page 71: ...2 0 04 in 57 5 1 0 mm 2 3 0 04 in e30bb595 11 PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 10 IP20 X3 V3 Internal Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3...

Page 72: ...0 mm 9 8 0 04 in e30be375 10 PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 12 IP20 X3 V3 External Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4 3 X2 2 X2 3 e3...

Page 73: ...4 0 04 in 353 0 1 0 mm 13 9 0 04 in e30bb593 11 PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 14 IP20 X4 V3 Internal Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3...

Page 74: ...0 04 in 338 5 1 0 mm 13 3 0 04 in e30be404 10 PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 16 IP20 X4 V3 External Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3...

Page 75: ...4 0 04 in 735 8 2 5 mm 29 0 0 10 in 370 0 1 0 mm 14 6 0 04 in 418 0 2 5 mm 16 5 0 10 in e30bb591 11 PE M8 15Nm Illustration 7 18 IP20 X5 V3 Internal Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3...

Page 76: ...29 0 10 in 9 2 5 mm 0 4 0 10 in e30be411 11 PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 20 IP20 X5 V3 External Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4...

Page 77: ...0 04 in 240 0 1 0 mm 9 4 0 04 in 90 7 1 0 mm 3 6 0 04 in PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 22 IP20 X6 V3 Internal Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2...

Page 78: ...1 0 10 in 405 2 5 mm 15 9 0 10 in e30bb590 11 PE M8 15Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 24 IP20 X6 V3 External Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X...

Page 79: ...0 1 0 mm 9 4 0 04 in 167 9 1 0 mm 6 6 0 04 in e30bb587 11 PE M12 25Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 26 IP20 X7 V3 Internal Fan X1 1 X1 2 X1 3 X2 1 X2 2 X2 3 A B X3...

Page 80: ...2 5 mm 17 4 0 10 in e30bb588 11 PE M12 25Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 28 IP20 X7 V3 External Fan A B X1 1 X1 2 X1 3 X2 1 X3 1 X4 1 X3 2 X4 2 X3 3 X4 3 X2 2 X2...

Page 81: ...0 1 0 mm 0 4 0 04 in 443 0 2 5 mm 17 4 0 10 in 800 0 4 0 mm 31 5 0 16 in 957 5 4 0 mm 37 7 0 16 in PE M12 25Nm Illustration 7 30 IP20 X8 V3 Internal Fan X1 1 X1 2 X1 3 X2 1 X2 2 X2 3 A B X3 1 X4 1 X3...

Page 82: ...2 5 mm 17 4 0 10 in e30bb586 11 PE M12 25Nm 8 holes must be used to fix the AHF with M8 screws Illustration 7 32 IP20 X8 V3 External Fan X1 1 X1 2 X1 3 X2 1 X2 2 X2 3 A B X3 1 X4 1 X3 2 X4 2 X3 3 X4...

Page 83: ...sions are valid for filters with both internal and external fan Always mount the AHF according to the definitions valid for the basic AHF IP20 unit 195 1 0 mm 7 7 0 04 in 141 7 1 0 mm 5 6 0 04 in 295...

Page 84: ...10 in 251 7 1 0 mm 9 9 0 04 in 34 7 mm 1 4 in 22 5 mm 0 9 in e30be455 10 Illustration 7 36 IP21 X2 V3 Internal and External Fan e30be456 10 Illustration 7 37 IP21 X2 V3 Internal and External Fan 3D Vi...

Page 85: ...n 80 8 1 0 mm 3 2 0 04 in 172 1 0 mm 6 8 0 04 in 67 5 1 0 mm 2 7 0 04 in 259 2 5 mm 10 2 0 10 in 353 2 5 mm 13 9 0 10 in 44 2 mm 1 7 in 28 4 mm 1 1 in 22 5 mm 0 9 in e30be459 10 Illustration 7 38 IP21...

Page 86: ...2 5 mm 13 0 10 in 353 2 5 mm 13 9 0 10 in 343 8 2 5 mm 13 5 0 10 in 89 6 2 5 mm 3 5 0 10 in 240 2 5 mm 9 4 0 10 in 22 5 mm 0 9 in 34 7 mm 1 4 in 63 3 mm 2 5 in e30be470 10 Illustration 7 40 IP21 X4 V...

Page 87: ...3 7 0 04 in 392 6 2 5 mm 15 4 0 10 in 345 2 5 mm 13 6 0 10 in 82 1 0 mm 3 2 0 04 in 210 5 2 5 mm 8 3 0 10 in 210 5 2 5 mm 8 3 0 10 in 34 7 mm 1 4 in 22 5 mm 0 9 in 63 3 mm 2 5 in Illustration 7 42 IP2...

Page 88: ...40 2 5 mm 9 4 0 10 in 84 7 1 0 mm 3 3 0 04 in 392 2 5 mm 15 4 0 10 in 410 2 5 mm 16 4 0 10 in 210 2 5 mm 8 3 0 10 in 20 5 mm 0 8 in 40 mm 1 6 in 25 5 mm 1 in Illustration 7 44 IP21 X6 V3 Internal and...

Page 89: ...4 0 10 in 240 2 5 mm 9 4 0 10 in 93 8 1 0 mm 3 7 0 04 in 443 2 5 mm 17 4 0 10 in 467 6 2 5 mm 18 4 0 10 in 83 8 2 5 mm 3 3 0 10 in 20 5 mm 0 8 in 40 mm 1 6 in 40 mm 1 6 in 40 mm 1 6 in Illustration 7...

Page 90: ...in 88 8 2 5 mm 3 5 0 10 in 443 2 5 mm 17 4 0 10 in 531 4 2 5 mm 20 9 0 10 in 78 8 2 5 mm 3 1 0 10 in 20 5 mm 0 8 in 20 mm 1 6 in 20 mm 1 6 in 20 mm 1 6 in e30be521 10 Illustration 7 48 IP21 X8 V3 Int...

Page 91: ...8 are shown in Illustration 7 51 e30bh260 10 A B D C E E F F 6 8 6 8 25 12 25 Enclosure X1 130B3283 mm in Enclosure X2 130B3284 mm in A 188 7 4 230 9 1 B 163 6 4 205 8 1 C 295 11 6 399 15 7 D 276 10 9...

Page 92: ...443 17 4 C 348 13 7 348 13 7 388 15 3 438 17 2 D 145 5 7 156 5 6 2 210 5 8 3 238 9 4 E 233 9 2 240 9 4 240 9 4 300 11 8 F 145 5 7 156 5 6 2 210 5 8 3 238 9 4 G 547 21 5 577 22 7 685 27 800 31 5 The t...

Page 93: ...ass J 600 V AC rated circuit breaker capacity 100 kA 19 35 Class J 600 V AC rated circuit breaker capacity 100 kA 25 50 Class J 600 V AC rated circuit breaker capacity 100 kA 31 50 Class J 600 V AC ra...

Page 94: ...rcuit breaker capacity 100 kA 240 400 Class J 600 V AC rated circuit breaker capacity 100 kA 296 500 Class J 600 V AC rated circuit breaker capacity 100 kA 366 600 Class J 600 V AC rated circuit break...

Page 95: ...dentified by revision number 03 Example SN 0100 03 378 Characters 5 and 6 are 03 confirming that this is revision number 03 A e30bh262 10 A Identification of revision number Illustration 8 1 Product L...

Page 96: ...U0135 Capacitor bank AHF2 DA B 400V 50Hz 014A 22 175U0136 Capacitor Bank AHF2 DA B 400V 50Hz 022A 29 175U0137 Capacitor Bank AHF2 DA B 400V 50Hz 029A 34 175U0138 Capacitor Bank AHF2 DA B 400V 50Hz 034...

Page 97: ...A B 380V 60Hz 480A Table 8 2 Capacitor Kits 380 415 V 60 Hz Valid for AHF revisions 01 and 02 440 480 V 60 Hz Capacitor kit Current rating A Order number P N Description 10 175U0152 Capacitor Bank AHF...

Page 98: ...id for AHF revisions 01 and 02 500 690 V 50 Hz Capacitor kit Current rating A Order number P N Description 15 175U0173 Capacitor bank AHF2 DA B 500V 690V 50Hz 015A 20 175U0174 Capacitor bank AHF2 DA B...

Page 99: ...acitor Bank AHF3 DA B 400V 50Hz 022A 29 175U1137 Capacitor Bank AHF3 DA B 400V 50Hz 029A 34 175U1138 Capacitor Bank AHF3 DA B 400V 50Hz 034A 40 175U1139 Capacitor Bank AHF3 DA B 400V 50Hz 040A 55 175U...

Page 100: ...6A Table 8 7 Capacitor Kits 380 415 V 60 Hz Valid only for AHF revisions 03 440 480 V 60 Hz Capacitor kit Current rating A Order number P N Description 10 175U1152 Capacitor Bank AHF3 DA B 380 460V 60...

Page 101: ...DA 600V 60Hz 395A Table 8 9 Capacitor Kits 600 V 60 Hz Valid only for AHF revisions 03 500 690 V 50 Hz Capacitor kit Current rating A Order number P N Description 15 175U1173 Capacitor Bank AHF3 DA B...

Page 102: ...2 29 175U0259 3 x 10 mm2 175U0257 3 x 2 5 mm2 175U0257 3 x 2 5 mm2 34 175U0260 3 x 16 mm2 175U0259 3 x 10 mm2 175U0257 3 x 2 5 mm2 40 175U0260 3 x 16 mm2 175U0259 3 x 10 mm2 175U0257 3 x 2 5 mm2 55 17...

Page 103: ...300 mm2 175U0264 3 x 95 120 mm2 175U0257 3 x 2 5 mm2 Table 8 12 Terminal Kits 440 480 V 60 Hz Valid for AHF revisions 01 02 and 03 600 V 60 Hz Terminals X1 X2 Terminals X3 X4 Terminals A B Current rat...

Page 104: ...0 3 x 16 mm2 175U0257 3 x 2 5 mm2 77 175U0263 3 x 70 mm2 175U0261 3 x 35 mm2 175U0257 3 x 2 5 mm2 87 175U0263 3 x 70 mm2 175U0261 3 x 35 mm2 175U0257 3 x 2 5 mm2 109 175U0263 3 x 70 mm2 175U0261 3 x 3...

Page 105: ...see Table 8 19 to Table 8 28 Valid only for AHF revisions 01 and 02 380 415 V 50 Hz 60 Hz Fan Fan fence Fan transformer Current rating A Quantity required Order number P N Description Quantity require...

Page 106: ...2 436 2 2 2 Table 8 16 Fan Kits and Accessories 440 480 V 60 Hz 1 10 A version is cooled by natural convections Valid only for AHF revisions 01 and 02 600 V 60 Hz Fan Fan fence Fan transformer Current...

Page 107: ...ber P N Description 15 1 175U0266 AHF2 Fan 600 690 V 1 175U0323 AHF2 Fan fence size 30 1 175U0269 Transformer for AHF2 600 V 690 V 230 V 20 1 1 1 24 1 1 1 29 1 1 1 36 1 1 1 50 1 1 1 58 1 1 1 77 1 1 1...

Page 108: ...N Description Quantity required Order number P N Description Quantity required Order number P N Description 10 X1 V3 IP20 if 0 2 0 0 14 X1 V3 IP20 ef 1 175U0338 AHF3 fan 24 V DC 1 175U0339 AHF3 fan f...

Page 109: ...if 1 0 1 40 X3 V3 IP20 if 1 0 1 55 X3 V3 IP20 if 1 0 1 66 X4 V3 IP20 if 1 0 1 82 X4 V3 IP20 ef 1 1 175U0339 AHF3 fan fence for 24 V DC fan 1 96 X5 V3 IP20 ef 1 1 1 133 X5 V3 IP20 ef 1 1 1 171 X6 V3 IP...

Page 110: ...3 IP20 if 1 0 1 55 X3 V3 IP20 if 1 0 1 66 X4 V3 IP20 if 1 0 1 82 X4 V3 IP20 ef 1 1 175U0339 AHF3 fan fence for 24 V DC fan 1 96 X5 V3 IP20 ef 1 1 1 133 X5 V3 IP20 ef 1 1 1 171 X6 V3 IP20 ef 1 1 1 204...

Page 111: ...20 if 1 0 1 55 X3 V3 IP20 if 1 0 1 66 X4 V3 IP20 if 1 0 1 82 X4 V3 IP20 ef 1 1 175U0339 AHF3 fan fence for 24 V DC fan 1 96 X5 V3 IP20 ef 1 1 1 133 X5 V3 IP20 ef 1 1 1 171 X6 V3 IP20 if 1 0 1 204 X6 V...

Page 112: ...3 IP20 if 1 0 1 48 X3 V3 IP20 if 1 0 1 60 X4 V3 IP20 if 1 0 1 73 X4 V3 IP20 ef 1 1 175U0339 AHF3 fan fence for 24 V DC fan 1 95 X5 V3 IP20 ef 1 1 1 118 X5 V3 IP20 ef 1 1 1 154 X6 V3 IP20 ef 1 1 1 183...

Page 113: ...if 1 0 1 36 X3 V3 IP20 if 1 0 1 48 X3 V3 IP20 if 1 0 1 60 X4 V3 IP20 if 1 0 1 73 X4 V3 IP20 ef 1 1 175U0339 AHF3 fan fence for 24 V DC fan 1 95 X5 V3 IP20 ef 1 1 1 118 X5 V3 IP20 ef 1 1 1 154 X6 V3 IP...

Page 114: ...ted in the cabinet Valid only for AHF 010 revision 03 600 V 60 Hz AHF 010 Fan Fan fence Fan control Current rating A Enclosure type1 Quantity required Order number P N Description Quantity required Or...

Page 115: ...an fence integrated in the cabinet Valid only for AHF 010 revision 03 500 690 V 50 Hz AHF 010 Fan Fan fence Fan control Current rating A Enclosure type1 Quantity required Order number P N Description...

Page 116: ...r number P N Description Order number P N Description Order number P N Description 10 10 10 1 1 1 1 1 1 14 14 14 15 15 175U0114 AHF Fuse for fan 380 690 V 2 A 175U0115 AHF Fuse holder 380 690 V 175U01...

Page 117: ...Fuse for fan 380 690 V 2 A 175U0115 AHF Fuse holder 380 690 V 175U0117 AHF Cover for fuse holder 380 690 V 20 20 24 24 29 29 36 36 50 50 58 58 77 77 87 87 109 109 128 128 155 155 197 197 240 240 296...

Page 118: ...wer Drive system PDS Complete drive module CDM Infeed section Auxiliaries Auxiliaries Motor Motor starter contactors soft starters Motor control system CDM or starter Driven equipment Trans mission Lo...

Page 119: ...d auxiliary equipment To get a configu ration specific power loss and efficiency data use the Danfoss MyDrive ecoSmart tool The power loss data is provided in of rated apparent output power and are de...

Page 120: ...n be used for system calculations and creating an energy efficiency report The tool can be found via www ecosmart danfoss com The power loss of the VLT Advanced Harmonic Filter AHF005 AHF010 is specif...

Page 121: ...wer loss Matching values from the tables in chapter 7 3 Power Loss and Acoustic Noise Level 86 W power loss at 10 A current loading 142 W power loss at 20 A current loading Determining the power loss...

Page 122: ...ective 5 Machinery Directive 5 6 RoHS Directive 5 Discharge time 7 93 Displacement angle 9 Displacement power factor 9 11 Distortion factor 11 E Efficiency Efficiency 117 class 116 Energy efficiency 1...

Page 123: ...t 103 106 Fan kit 103 106 Fuse kit 114 Terminal kit 100 Transformer 103 106 Standards G5 4 12 IEC 61000 2 2 12 IEC 61000 2 4 12 IEC 61800 9 2 116 117 IEC EN 61000 3 12 12 IEC EN 61000 3 2 12 IEC EN 61...

Page 124: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Reviews: