Selection table, 380–415 V, 50 Hz
Drive values
AHF values
Power rating
[kW]
1)
Input
current
380–440 V
[A]
Current
rating
[A]
Order numbers
3)
Enclosure type
AHF 005 IP20
AHF 010 IP20
AHF 005 IP20
AHF 010 IP20
0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.0
1.2
1.6
2.2
2.7
3.7
5.0
6.5
9.0
10
130B1229
130B1027
X1-V3 IP20 if
X1-V3 IP20 if
5.5
7.5
11.7
14.4
14
130B1231
130B1058
X1-V3 IP20 ef
X1-V3 IP20 ef
11
22
22
130B1232
130B1059
X2-V3 IP20 ef
X2-V3 IP20 if
15
29
29
130B1233
130B1089
X2-V3 IP20 ef
X2-V3 IP20 if
18.5
34
34
130B1238
130B1094
X3-V3 IP20 if
X3-V3 IP20 if
22
40
40
130B1239
130B1111
X3-V3 IP20 if
X3-V3 IP20 if
30
55
55
130B1240
130B1176
X3-V3 IP20 if
X3-V3 IP20 if
37
66
66
130B1241
130B1180
X4-V3 IP20 if
X4-V3 IP20 if
45
82
82
130B1247
130B1201
X4-V3 IP20 ef
X4-V3 IP20 ef
55
96
96
130B1248
130B1204
X5-V3 IP20 ef
X5-V3 IP20 ef
75
133
133
130B1249
130B1207
X5-V3 IP20 ef
X5-V3 IP20 ef
90
171
171
130B1250
130B1213
X6-V3 IP20 ef
X6-V3 IP20 if
110
204
204
130B1251
130B1214
X6-V3 IP20 ef
X6-V3 IP20 if
132
251
251
130B1258
130B1215
X7-V3 IP20 if
X7-V3 IP20 if
160
304
304
130B1259
130B1216
X7-V3 IP20 if
X7-V3 IP20 if
–
–
325
130B3152
4)
130B3136
4)
X8-V3 IP20 if
X7-V3 IP20 if
200
381
381
130B1260
130B1217
X8-V3 IP20 ef
X7-V3 IP20 if
250
463
480
130B1261
130B1228
X8-V3 IP20 ef
X8-V3 IP20 ef
315
590
608
2 x 130B1259
2 x 130B1216
See individual filters
355
647
650
2 x 130B3152
2 x 130B3136
400
684
685
13
130B1260
13
130B1217
450
779
762
2 x 130B1260
2 x 130B1217
500
857
861
13
130B1261
13
130B1228
560
964
960
2 x 130B1261
2 x 130B1228
630
1090
1140
3 x 130B1260
3 x 130B1217
710
1227
1240
2 x 13
130B1261
2 x 13
130B1228
800
1422
1440
3 x 130B1261
3 x 130B1228
1000
1675
1720
2 x 13
2 x 130B1261
2 x 13
2 x 130B1228
Table 5.3 Frequency Converters with Voltage Classes T4 and T5, Operating at 380–415 V, 50 Hz
1) The power ratings in the selection table are the actual operating power and not necessarily the type code power rating.
Changing operating conditions between HO and NO changes the actual operating conditions and the filter selection must reflect the actual
operating conditions.
2) Typical hp shaft output at 460 V.
3) The fan control system allows extended input voltage range as 200–415 V. The AHFs for 380–415 V/50 Hz mains operation can be operated
with 200–240 V mains supply.
4) Filters are used as paralleling for 355 kW drive.
Selection of Advanced Harmo...
VLT
®
Advanced Harmonic Filter AHF 005/AHF 010
28
Danfoss A/S © 05/2019 All rights reserved.
MG80C602
5
5
Summary of Contents for AHF 010