Selection table, 500–690 V, 50 Hz
Drive values
AHF values
Power
rating
Input current
Current rating
at 690 V
Order numbers
Enclosure type
[kW]
1)
T6
525–550 V
[A]
T7
525–550 V
[A]
T7
690 V
[A]
AHF 005
[A]
AHF 010
[A]
AHF 005
IP20
AHF 010
IP20
AHF 005
IP20
AHF 010
IP20
11
17.2
15.0
14.5
15
15
130B5088
130B5280
X3-V3 IP20 if
X3-V3 IP20 if
15
20.9
19.5
19.5
20
20
130B5089
130B5281
X3-V3 IP20 if
X3-V3 IP20 if
18.5
25.4
24
24
24
24
130B5090
130B5282
X3-V3 IP20 ef
X3-V3 IP20 ef
22
32.7
29
29
29
29
130B5092
130B5283
X4-V3 IP20 ef
X4-V3 IP20 ef
30
39.0
36
36
36
36
130B5125
130B5284
X4-V3 IP20 ef
X4-V3 IP20 ef
37
49.0
49
48
50
50
130B5144
130B5285
X5-V3 IP20 ef
X5-V3 IP20 ef
45
59.0
59
58
58
58
130B5168
130B5286
X5-V3 IP20 ef
X5-V3 IP20 ef
55
78.9
77
77
77
77
130B5169
130B5287
X6-V3 IP20 ef
X6-V3 IP20 ef
75
95.3
89
87
87
87
130B5170
130B5288
X6-V3 IP20 ef
X6-V3 IP20 ef
90
124.3
110
109
109
109
130B5172
130B5289
X6-V3 IP20 ef
X6-V3 IP20 ef
110
–
130
128
128
128
130B5195
130B5290
X6-V3 IP20 ef
X6-V3 IP20 ef
132
–
158
155
155
155
130B5196
130B5291
X7-V3 IP20 ef
X7-V3 IP20 ef
160
–
198
197
197
197
130B5197
130B5292
X7-V3 IP20 ef
X7-V3 IP20 ef
200
–
245
240
240
240
130B5198
130B5293
X8-V3 IP20 ef
X7-V3 IP20 ef
250
–
299
296
296
296
130B5199
130B5294
X8-V3 IP20 ef
X8-V3 IP20 ef
315
–
355
352
394
366
2 x 130B5197
130B5295
See individual
filters
X8-V3 IP20 ef
355
–
381
366
394
395
2 x 130B5197
130B5296
X8-V3 IP20 ef
400
–
413
400
437
437
13
130B5198
13
130B5293
See individual filters
500
–
504
482
536
536
13
130B5199
13
130B5294
560
–
574
549
592
592
2 x 130B5199
2 x 130B5294
630
–
642
613
662
662
13
2 x 130B5197
13
130B5295
710
–
743
711
788
732
4 x 130B5197
2 x 130B5295
800
–
866
828
888
888
3 x 130B5199
3 x 130B5294
900
–
962
920
986
958
2 x 130B5199
+ 2 x
130B5197
2 x 130B5294
+130B5295
Table 5.7 Frequency Converters with Voltage Classes T6 and T7, Operating at 500–690 V, 50 Hz
1) The power ratings in selection table are the actual operating power and not necessarily the type code power rating.
Changing operating conditions between HO and NO changes the actual operating conditions and the filter selection must reflect actual operating
conditions.