5.2.1 Capacitor Disconnect Contactors
Selection table for VLT
®
Advanced Harmonic Filters AHF 005/AHF 010 using separate Danfoss contactors.
AHF current rating
AHF
enclosure
size
type
Danfoss contactors
380–415 V
50 Hz
380–415 V
60 Hz
440–480 V
60 Hz
600 V
60 Hz
500–690 V
50 Hz
AHF
005
[A]
AHF
010
[A]
AHF
005
[A]
AHF
010
[A]
AHF
005
[A]
AHF
010
[A]
AHF
005
[A]
AHF
010
[A]
AHF
005
[A]
AHF
010
[A]
Description
Order
number
10
14
10
14
10
14
10
14
10
14
10
14
–
–
–
–
X1
CI 9
037H0021.32
22
29
22
29
22
29
22
29
19
25
19
25
–
–
–
–
X2
CI 16
037H0041.32
34
40
55
34
40
55
34
40
55
34
40
55
31
36
48
31
36
48
15
20
24
15
20
24
15
20
24
15
20
24
X3
CI 30
037H0055.32
66
82
66
82
66
82
66
82
60
73
60
73
29
36
29
36
29
36
29
36
X4
CI 45
037H0071.32
96
133
96
133
96
133
96
133
95
118
95
118
50
58
50
58
50
58
50
58
X5
CI 61
037H3061.32
171
204
171
204
171
204
171
204
154
183
154
183
77
87
109
128
77
87
109
128
77
87
109
128
77
87
109
128
X6
CI 98
037H3040.32
251
304
251
304
325
381
251
251
304
325
381
231
231
291
355
380
155
197
155
197
240
155
197
155
197
240
X7
CI 180
037H3082.31
325
381
–
304
325
381
–
291
355
380
–
240
296
296
366
240
296
296
366
X8
CI 180
037H3082.31
480
480
480
480
436
436
–
395
–
395
X8
CI 250
037H3267.32
Table 5.8 Selection Table, Capacitor Disconnect Contactors - Danfoss Types
5.2.1.1 Non-Danfoss Contactors
Non-Danfoss contactors are compatible with the VLT
®
Advanced Harmonic Filter AHF 005/AHF 010. If using non-Danfoss
contactors for capacitor disconnect, always select AC3-types. The current rating of the contactor must be equal to or higher
than 50% of the nominal current rating of the AHF.
If the contactor is controlled by external equipment and not by a specific parameter in a Danfoss frequency converter, use
contactors for capacitive switching.
Selection of Advanced Harmo...
Design Guide
MG80C602
Danfoss A/S © 05/2019 All rights reserved.
33
5
5
Summary of Contents for AHF 010
Page 2: ......