5-13 Terminal 29 Digital Input
Select the function from the available digital input range and the
additional options
[60] Counter A
,
[61] Counter A
,
[63] Counter B
,
and
[64] Counter B
. Counters are used in smart logic control
functions.
Option:
Function:
[70]
Mech. Brake
Feedb.
[71]
Mech. Brake
Feedb. Inv.
[72]
PID error
inverse
[73]
PID reset I
part
[74]
PID enable
[75]
MCO Specific
[78]
Reset Maint.
Word
[80]
PTC Card 1
[91]
Profidrive
OFF2
[92]
Profidrive
OFF3
[94]
Light Load
Detection
[96]
Mains Loss
[97]
Mains Loss
Inverse
[98]
Start edge
triggered
[100]
Safe Option
Reset
[107]
Target Inverse
[108]
Enable Master
Offset
[109]
Start Virtual
Master
[110]
Start Homing
[111]
Activate Touch
[112]
Relative
Position
[113]
Enable
Reference
[114]
Sync. to Pos.
Mode
[115]
Home Sensor
[116]
Home Sensor
Inv.
[117]
Touch Sensor
[118]
Touch Sensor
Inv.
[119]
Speed Mode
[231]
Power Limit
Mot.
[232]
Power Limit
Gen.
5-13 Terminal 29 Digital Input
Select the function from the available digital input range and the
additional options
[60] Counter A
,
[61] Counter A
,
[63] Counter B
,
and
[64] Counter B
. Counters are used in smart logic control
functions.
Option:
Function:
[233]
Power Limit
Both
6.1.2 5-3* Digital Outputs
5-30 Terminal 27 Digital Output
This manual only shows the option relevant for the VLT
®
Advanced Harmonic Filter AHF 005/AHF 010. Refer to the
frequency converter programming guide for the complete list of
options in this parameter.
Option:
Function:
[188] AHF Capacitor
Connect
NOTICE
This function is not suitable when
multiple frequency converters are
connected to a single filter.
The capacitors are turned on at 20%
(hysteresis of 50% gives an interval of
10–30%). The capacitors are discon-
nected below 10%. The off delay is 10 s
and restarts if the nominal power goes
above 10% during the delay.
Parameter 5-80 AHF Cap Reconnect
Delay
is used to guarantee a minimum
off-time for the capacitors.
5-40 Function Relay
This manual only shows the option relevant for the VLT
®
Advanced Harmonic Filter AHF 005/AHF 010. Refer to the
frequency converter programming guide for the complete list of
options in this parameter.
Option:
Function:
[188] AHF Capacitor
Connect
NOTICE
This function is not suitable when
multiple frequency converters are
connected to a single filter.
The capacitors are turned on at 20%
(hysteresis of 50% gives an interval of
10–30%). The capacitors are discon-
nected below 10%. The off delay is 10 s
and restarts if the nominal power goes
above 10% during the delay.
Parameter 5-80 AHF Cap Reconnect Delay
is used to guarantee a minimum off-
time for the capacitors.
Programming
Design Guide
MG80C602