7.4.1 Terminal Specifications
to
show the terminal types, cable cross-section, tightening torque, and more.
NOTICE
The maximum cable cross-sections in tables
to
are for solid cables. The maximum cross-sections for
multi-core cables can be seen in the terminal specifications on the illustrations in
.
AHF terminal connections
380–415 V
50 Hz
Enclosure
size
Type
Terminals X1 and X2
Terminals X3 and X4
Terminals A and B
PE
AHF
005
[A]
AHF
010
[A]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Type
Torque
[Nm (in-
lb)]
10
14
10
14
X1
0.5–10
(20–8)
Cable
end
sleeve
1.6 (14.2)
±
10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±
10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±
10%
M6
4.5 (40)
±
10%
22
29
22
29
X2
1.5–16
(16–6)
2.4 (21.2)
±
10%
0.5–4
(20–12)
0.8 (7.1)
±
10%
M6
4.5 (40)
±
10%
34
40
55
34
40
55
X3
1.5–25
(16–4)
3.5 (31)
±
10%
1.5–16
(16–6)
2.4 (21.2)
±
10%
M8
10 (88.5)
±
10%
66
82
66
82
X4
1.5–50
(16–
1-1/0)
4 (35.4)
±
10%
1.5–25
(16–4)
3.5 (31)
±
10%
M8
10 (88.5)
±
10%
96
133
96
133
X5
10–70
(8–2/0)
5 (44.3)
±
10%
1.5–25
(16–4)
3.5 (31)
±
10%
M8
10 (88.5)
±
10%
171
204
171
204
X6
2.5–95
(14–3/0)
Cable lug
M8
10 (88.5)
±
10%
1.5–50
(16–
1-1/0)
4 (35.4)
±
10%
M8
10 (88.5)
±
10%
251
304
251
304
325
381
X7
25–300
(4–600)
Cable lug
M16
50 (442.5)
±
10%
16–150
(6–300)
18
(159.3)
±
10%
M12
40 (354)
±
10%
325
381
480
480
X8
25–300
(4–600)
Cable lug
M16
50 (442.5)
±
10%
16–150
(6–300)
18
(159.3)
±
10%
M12
40 (354)
±
10%
Table 7.19 Terminal Specifications, 380–415 V, 50 Hz
Specifications
VLT
®
Advanced Harmonic Filter AHF 005/AHF 010
60
Danfoss A/S © 05/2019 All rights reserved.